2002-01-10 00:00:00TRUSSES DENIED
  
 1) THE TRUSS DRAWINGS REFERENCE ASCE7-98
 THIS IS NOT THE CORRECT DESIGN CRITERIA,
 FOR THE CODE CURRENTLY ADOPTED BY THE
 CITY OF WPB.THE TRUSSES MUST BE DESIGNED
 USING ASCE 7-95 (145 MPH) OR 1997 SBC
 SECTION 1606 (110 MPH). THE TRUSS COVER
 SHEET LISTS ASCE 7-95 AND 150MPH. PLEASE
 CORRECT THIS TO BE CONSISTENT WITH THE
 TRUSS DRAWINGS.
  
 2) THE WIND DESIGN VELOCITY LISTED ON
 THE TRUSS LAYOUT IS 110 MPH. THIS IS NOT
 CONSISTENT WITH THE TRUSS DRAWINGS. THE
 STRUCTURE IS DESIGNED TO ASCE 7-95 (145
 MPH), THEREFORE THE TRUSSES MUST MEET
 THIS CRITERIA.
  
 3) PLEASE REVIEW THE CONNECTOR FOR TRUSS
 TG1.THE UPLIFT AT JOINT 1 IS 4470# AND
 THE CONNECTOR SPECIFIED IS TA-5 RATED
 FOR 2490# UPLIFT. PLEASE CORRECT.
  