Plan Review Notes
Plan Review Notes For Permit 01091666
Permit Number 01091666
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-13 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) BATHROOMS DO NOT COMPLY WITH FAIR
 HOUSING ACT. IF SPECIFICATION A IS
 SELECTED AS THE BASIS FOR DESIGNING A
 BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT MUST COMPLY WITH THE A SPECIFICAT-
 IONS. ALL FIXTURES MUST BE USABLE IN A
 SPECIFICATION A BATHROOM.(7.34) INDICATE
 GRAB BARS IN THE SHOWER. PROVIDE A
 30"X 48" CLEAR SPACE CENTERED ON THE
 BASIN AT BOTH LAVATORIES. BOTH ARE
 REQUIRED TO BE USABLE. A LAVATORY, ANY
 OTHER FIXTURE OR WING WALL MUST NOT
 PROJECT INTO ROOM ANY MORE THAN 24" WHEN
 OVERLAPPING THE CLEAR SPACE AT TOILETS.
 (7.43) PLEASE CORRECT.
  
 3) THE OPENING SQ.FT. AND THE PRESSURES
 ARE INCORRECT FOR ONE OF THE LIVING ROOM
 WINDOWS. PLEASE CORRECT.
  
 4) THE 16" DEEP FOOTINGS INDICATED ON
 THE PLANS WILL NOT COMPLY WITH THE 14"
 BELOW FINAL GRADE REQUIRED BY THE SOIL
 REPORT AND THE CITY AMENDMENTS REQUIRING
 4" ABOVE FINISH GRADE. PLEASE CORRECT.
  
 5) THE REQUIRED WINDLOADS FOR THE BED
 ROOM AND THE BATHROOM EXCEED THE DESIGN
 LOADS FOR THE WINDOW PRODUCT APPROVALS
 THAT WERE SUBMITTED. PLEASE CORRECT.
  
 6) THE PRODUCT APPROVALS FOR THE GLASS
 BLOCK THAT WERE SUBMITTED, EXPIRED PRIOR
 TO APPLYING FOR PERMIT.
  
 7) THE PRODUCT APPROVALS FOR THE STORM
 PANELS WERE MISSING FROM THE SUBMITTAL.
  
  
 TRUSSES
 UNSAT
  
 1) TRUSS TG1 IS INDICATED ON TRUSS
 DRAWING WITH AN UPLIFT OF 4502# AT
 JOINT 2 AND THE PLANS INDICATE (2) TA-14
 (TAPR 216) RATED AT 1450# EACH PER YOUR
 ANCHOR SCHEDULE. PLEASE REVIEW.
  
 2) TRUSS TG6 IS LISTED ON THE TRUSS
 DRAWINGS WITH AN UPLIFT OF 4003#. THE
 PLANS INDICATE T-11 ANCHOR (2- TAPR 216)
 RATED AT 3900# PER YOUR ANCHOR SCHEDULE.
 PLEASE REVIEW.
  
 NOTE: SEMCO AND HUGHES HAVE BEEN
 PURCHASED BY USP. SOME OF THE PRODUCTS
 WILL BE DISCONTINUED AND OTHERS MAY HAVE
 LOAD VALUES THAT HAVE CHANGED.
 YOU HAVE THE UPLIFT VALUE OF 1950# FOR
 A TAPR 216 WITH (11) 16D NAILS AND THE
 2001 USP CATALOG LISTS THE UPLIFT VALUE
 AS 1485#. YOUR SCHEDULE INDICATES THE
 UPLIFT VALUES DOUBLE FOR TWO CONNECTORS,
 HOWEVER, THE VALUES ARE REDUCED IF THE
 ANCHORS ARE LOCATED WITHIN 8" OF EACH
 OTHER PER THE CATALOG. THE SCHEDULE
 INCORRECTLY LISTS THE LENGTH OUT OF
 CONCRETE FOR TA-14 (TAPR 216) AS 14".
 PROVIDE THE CRITERIA USED TO DETERMINE
 THE LOADS WHEN TYPE OR AMOUNT OF
 FASTENERS IS DIFFERENT THAN THOSE LISTED
 IN THE CATALOG. PLEASE PROVIDE A
 CORRECTED SCHEDULE.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202