Plan Review Notes
Plan Review Notes For Permit 01091662
Permit Number 01091662
Review Stop R
Sequence Number 1
Notes
Date Text
2001-10-30 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT
 WITH THE COURHOUSE.
 2-AFTER ORIGINAL DRAWINGS ARE REVISED,
 PLEASE BRING THEM TO PALM BEACH COUNTY
 TO PAY IMPACT FEES. BRING STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS INCOMPLETE:
 A)INDICATE EXPOSURE CONDITION.
 B)REVISE THE IMPORTANCE FACTOR: SEE
 ASCE 7-95 TABLE 6-2.
 C)ENGINEER DIDN'T SIGN THE FORM.
  
 4-THIS PROPERTY IS LOCATED ON FLOOD ZONE
 A-5. PROVIDE SURVEY SHOWING EXISTING
 FINISH FLOOR ELEVATIONS TO VERIFY THAT
 LOWEST FLOOR IS 6" ABOVE THE BASE
 FLOOD ELEVATION. SEC. 12-22(B)(1) OF
 CITY CODE.
 5-PROVIDE SITE PLAN SHOWING LOCATION OF
 GARAGE IN RELATION TO PROPERTY LINE TO
 CHECK FOR TABLE 600 SBC 1997.
 6-PROVIDE COMPLETE FASTENING SPECS FOR
 ATTACHMENT OF NEW PORTION OF CHIMNEY
 TO EXISTING ONE.
 -ALSO, CHIMNEY DETAIL/SECTION DOESN'T
 MATCH THE ONE SHOWN ON EXT. ELEVATIONS
 -PROVIDE PRODUCT APPROVAL AND SPECS FOR
 "DUROCK" MATERIAL USED AS WALL AND
 ROOF SHEATHING MATERIAL.
 7-REVISE GENERAL NOTES. THEY SAY THAT
 THE DESIGN CRITERIA IS SSTD 10-97, BUT
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM SEALED BY THE ENGIN'R
 USES ASCE 7-95 FOR 150 MPH WIND LOAD.
 SSTD 10-97 IS NOT A BUILDING CODE. IT
 IS A DESIGN PRESCRIPTIVE METHOD USED
 WHEN THE DESIGNER IS NOT A REGISTERED
 ARCHITECT OR ENGINEER.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SECTION 2405.2 SBC 1997.
 9-PROVIDE,2 COPIES,PRODUCT APPROVAL FOR:
 A)SPANISH TILE.
 B)FRENCH DOORS.
 C)SINGLE HUNG WINDOWS.
 D)ENTRY DOORS.
 E)UL LISTING AND SPECS FOR BBQ.
 F)GARAGE DOORS.
 10-PROVIDE PRODUCT APPROVALS FOR STORM
 SHUTTERS.
 -PROVIDE KEY PLAN AND COMPLETE INSTALL-
 ATION SCHEDULE AS PER CITY SAMPLE.
 -CLEARLY IDENTIFY ON PRODUCT APPROVALS
 SPECIFIC MOUNTING CONDITIONS AND
 ANCHORS TO BE USED.
 11-PROVIDE SMOKE DETECTORS BY STAIRS OF
 FLORIDA ROOM. SEC. 905.2 SBC 1997.
 12-SPECIFY CONNECTORS AT TOP AND BOTTOM
 OF NEW 2X4 COLUMNS AT KITCHEN AREA.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 13-SEE SECTION 1007 OF SBC 1997 AND
 PROVIDE ALL INFORMATION MISSING FOR
 STAIRS, RAILINGS, ETC.
 -SEE SECTION 2305 SBC 1997 AND PROVIDE
 THE SPECS FOR FIREBLOCKING.
 14-PROVIDE COMPLETE SECTION/DETAIL THRU
 MASTER BEDROOM BALCONY. INCLUDE SPECS
 FOR GUARDRAILS AS REQUIRED BY SECTIONS
 1015 AND 1608.2 SBC 1997.
 15-PROVIDE BORING TEST. SEC. 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997 AND
 GENERAL NOTES ON SHEET A-4.
 16-PROVIDE ATTIC ACCESS AT MASTER BEDRM
 AND GUEST SUITE. SEC. 2309.6 SBC 1997
 17-REVISE ENERGY CALCULATIONS:
 -USE FORM 600A-97, NOT 600A-93.
 -SPECIFY SIZE OF CEILING FANS ON ELEC.
 PLANS FOR MASTER BEDROOM, FAMILY ROOM
 AND GUEST SUITE IF USING THE CEILING
 FAN CREDIT ON ENERGY CALCULATIONS.
 SEE TABLE 6-6 OF FLORIDA ENERGY CODE
 FOR BUILDING CONSTRUCTION, 1997 ED.
 18-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING THOSE BY THE OTHER TRADES.
  
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE THE REVIEW.