2001-10-16 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCE SPC-94 SEC 104.3
 (1) SHT A-4 GUEST SUITE ABOVE GARAGE,
 PROVIDE ISOMETRIC OF DWV SYSTEM AND TIE-
 IN TO SANI SEWER.
 (2A) SHT A-5 SHOW LOCATION OF SINK AT
 REAR PORCH ON FLAT PLAN.
 (B) ISOMETRIC DOES NOTMATCH FLAT PLAN,
 MIN PIPE SIZE FOR SHOWER 2".
 MIN PIPE SIZE FOR BATH TUB 1-1/2"
 ISOMETRIC NOT ACCEPTABLE, RECOMMEND YOU
 HAVE A PLUMBER, MAKE THE DRAWING.
 (3)IF NO BACKFLOW PREVENTER ON WATER
 SERVICE, RPZV WILL BE REQUIRED.
 LOCAL ORDINANCE. #2893-95
 END OF COMMENTSPAUL SCHMITZ