| Plan Review Notes For Permit 01091662 |
| Permit Number |
01091662 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-16 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | CODE REFERENCE SPC-94 SEC 104.3 | | | (1) SHT A-4 GUEST SUITE ABOVE GARAGE, | | | PROVIDE ISOMETRIC OF DWV SYSTEM AND TIE- | | | IN TO SANI SEWER. | | | (2A) SHT A-5 SHOW LOCATION OF SINK AT | | | REAR PORCH ON FLAT PLAN. | | | (B) ISOMETRIC DOES NOTMATCH FLAT PLAN, | | | MIN PIPE SIZE FOR SHOWER 2". | | | MIN PIPE SIZE FOR BATH TUB 1-1/2" | | | ISOMETRIC NOT ACCEPTABLE, RECOMMEND YOU | | | HAVE A PLUMBER, MAKE THE DRAWING. | | | (3)IF NO BACKFLOW PREVENTER ON WATER | | | SERVICE, RPZV WILL BE REQUIRED. | | | LOCAL ORDINANCE. #2893-95 | | | END OF COMMENTSPAUL SCHMITZ | | | 561-659-8096X8233 |
|