| Date |
Text |
| 2001-10-09 00:00:00 | **************** UNSAT ************** |
| | |
| | 1)NOTE:PLEASE CALRIFY EQUIP GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF |
| | DISCONNECTAND PANEL(S). EQUIPMENT |
| | GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | MISSING ONE ON LOWER-LEVEL. |
| | |
| | |
| | 4)NOTE: PLEASE NOTE OUTLETS MISSING FOR |
| | KITCHEN ISLAND. PER 210-52-C-2.(GFI) |
| | |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6)NOTE: PLEASE NOTE MISSING WHIRLPOOL |
| | ON PANEL SCHEDULE/LOAD CALCS. |
| | |
| | 7)NOTE: PLEASE CLARIFYGROUNDING AT |
| | DETACHED GARAGE PER 250-32 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |