2001-10-09 00:00:00**************** UNSAT **************
  
 1)NOTE:PLEASE CALRIFY EQUIP GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING ONE ON LOWER-LEVEL.
  
  
 4)NOTE: PLEASE NOTE OUTLETS MISSING FOR
 KITCHEN ISLAND. PER 210-52-C-2.(GFI)
  
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE NOTE MISSING WHIRLPOOL
 ON PANEL SCHEDULE/LOAD CALCS.
  
 7)NOTE: PLEASE CLARIFYGROUNDING AT
 DETACHED GARAGE PER 250-32
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW