Plan Review Notes
Plan Review Notes For Permit 01091635
Permit Number 01091635
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-02 00:00:00*******************DENIED***************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING IN
 FORMATION FOR REVIEW.
  
 1.INDICATE MANUFACTURER, MODEL, BTU'S
 OF AHU.
  
 2.EXPLAIN WHY EXISTING 2 - 3 TON UNITS
 ARE BEING REPLACED BY 5 TON UNITS.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 4.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLAINCE WITH 1997 SMC 501.2.
  
 5.INDICATE ANY ADDITIONAL DUCTWORK
 AND COMPLETE SCOPE OF WORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388