| Plan Review Notes For Permit 01091635 |
| Permit Number |
01091635 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-02 00:00:00 | *******************DENIED*************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE PROVIDE THE FOLLOWING IN | | | FORMATION FOR REVIEW. | | | | | | 1.INDICATE MANUFACTURER, MODEL, BTU'S | | | OF AHU. | | | | | | 2.EXPLAIN WHY EXISTING 2 - 3 TON UNITS | | | ARE BEING REPLACED BY 5 TON UNITS. | | | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 4.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLAINCE WITH 1997 SMC 501.2. | | | | | | 5.INDICATE ANY ADDITIONAL DUCTWORK | | | AND COMPLETE SCOPE OF WORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388 |
|