| Notes |
| Date |
Text |
| 2001-10-19 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT UNDER 230-2 | | | UNLESS THE EXCEPTIONS ARE MET, THE NEW | | | SERVICE SHOWN COMING FROM FPL, IS NOT | | | PERMITTED. PLEASE CLARFIY # OF MAINS | | | THAT ARE EXISTING AND AND SIZE OF EXIST- | | | -ING SERVICE.? | | | PLEASE NOTE THAT PLANS ARE SHOWING A | | | NEW SEPARATE SERVICE RUNNING UP TO | | | A ROOM WITH EXISTING SERVICE. PLEASE | | | CLARIFY 2HR SEPARATION FROM EXSITING | | | SERVICE, IF A NEW SERVICE IS PERMITTED?? | | | IT APPEARS THAT THERE WILL BE ELECTRICAL | | | EQUIPMENT FEEDING THE SAME AREA AND ITEM | | | -S FROM TWO SERVICES?? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|