2001-10-11 00:00:00IT HAS BEEN EXPLAINED TO THIS WRITER
 THAT THE BUILDING IS A MIXED OCCUPANCY
 CONTAINING THREE SEPARATE OCCUPANCIES,
 TENANT 1 WAS EXPLAINED AS BUSINESS,
 TENANT 2 WAS EXPLAINED AS STORAGE,
 AND TENANT 3 INDUSTRIAL. NO MECHANICAL
 OR HVAC INFORMATION PROVIDED WITH
 PLANS.
 TENANT # 1
 A) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 TENANT # 2
 A) NO EMERGENCY LIGHTING SHOWN.
 B) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 TENANT # 3
 A) NO INFORMATION ON SEPARATION WALL
 FOR BETWEEN TENANT # 2 AND TENANT # 3.
 B) NO EMERGENCY LIGHTING SHOWN.
 C) SPRAY BOOTH CANNOT BE APPROVED
 BECAUSE NOT ENOUGH INFORMATION HAS
 BEEN PROVIDED. MAKE-UP AIR, DISCHARGE
 OF EXHAUST DUCT ON RAILROAD EASEMENT,
 REQUIRED 3 FOOT SEPARATION DISTANCE FROM
 SPRAY BOOTH. BOOTH GOING TO BE
 GROUNDED?
  