| Notes |
| Date |
Text |
| 2002-09-26 00:00:00 | THE REQUIRED FIRE PUMP WILL BE REQUIRED | | | TO PROVIDE AT LEAST 750 GPM AT THE | | | ROOF AT 65 PSI RESIDUAL PRESSURE AT THE | | | SAME LOCATION. THE FIRE PUMP AND | | | APPURTENANT EQUIPMENT ARE TO BE | | | INSTALLED IN ACCORDANCE WITH NFPA 20. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|