| | PLAN SHEET M-8 GENERAL NOTES #1. A., |
| | ALL WORK SHALL BE IN ACCORDANCE WITH |
| | SOUTH FLORIDA BUILDING CODE.PLANS ARE |
| | REVIEWED UNDER THE 1997 STANDARD |
| | MECHANICAL CODE NOT THE SOUTH FLORIDA |
| | BUILDING CODE. |
| | |
| | PLAN SHEET M-5 DETAILS FOR DRYER |
| | EXHAUST, AS PER 1997 SMC 509.3 |
| | RESIDENTIAL DRYER EXHAUST SHALL BE A |
| | MAXIMUM OF 25 FT WITH A 5 FT REDUCTION |
| | FOR EACH 90 DEGREE BEND AND 2 1/2 FT |
| | REDUCTION FOR EACH 45 DEGREE BEND. |
| | DRYER EXHAUST IS GREATER THAN THE 25 FT |
| | ALLOWANCE.INDICATE HOW COMBUSTIBLE |
| | LINT IS TO BE REMOVED FROM THE DRYER |
| | EXHAUST. |
| | |
| | PLEASE NOTE ON THE TOILET EXHAUST RISER |
| | AS PER COUNTYWIDE AMENDMENTS 1997 SMC |
| | 610.1.3 #2, SUBDUCT MUST BE A MINIMUM |
| | OF 26 GA. GALVANIZED OR EQUIVALENT. |
| | RISERS WHICH ARE SUBJECT TO MOISTURE |
| | SHALL BE LINED WITH SUITABLE MATERIAL |
| | TO PREVENT DETERIORATION OF DRYWALL |
| | ENCLOSURE. WHERE BRANCH DUCTS CONNECT TO |
| | RETURN RISERS, SUBDUCT SHALL BE CARRIED |
| | UPWARD 22" INSIDE THE RISER DUCT. |
| | |