| 2002-02-26 00:00:00 | A) PLEASE INDICATE ON THE DRAWINGS |
| | THAT THE TRASH CHUTE CAP WILL BE AT |
| | LEAST THREE FEET ABOVE THE ROOF OF |
| | THE BUILDING. RE: NFPA 82, SECTION |
| | 3-2.2.4. |
| | B) THE TRASH ROOM MUST BE AT LEAST |
| | TWO HOUR RATED WITH OPENING PROTECTIVES |
| | OF AT LEAST 1 1/2 RATINGS. RE: NFPA |
| | 82, SECTION 3-2.4.3. |
| | C) IT APPEARS THAT A PORTION OF THE |
| | UNDERGROUND FIRE LINE RUNS UNDERNEATH |
| | THE BUILDING'S FOUNDATION. THIS IS |
| | NOT PERMITTED. RE: NFPA 24, SECTION |
| | 8-3.1. |
| | D) ADDRESS REQUIRED ON BUILDING. |
| | E) CANVAS CANOPIES ARE TO BE FIRE |
| | RETARDANT. |
| | F) ROOF MANIFOLDS ARE REQUIRED ON THE |
| | ROOF. THE PLANS MAKE AT LEAST ONE |
| | REFERENCE TO FIRE DEPARTMENT CONNECTIONS |
| | BEING LOCATED ON THE ROOF. |
| | G) THE FIREFIGHTERS SMOKE CONTROL OR |
| | REMOVAL PANEL SHOULD BE LABELED WITH |
| | STAIRWELL LOCATIONS AND ANY OTHER |
| | LABELS THAT HELP PUT THE BUILDING INTO |
| | SOME ORIENTATION WITH REGARDS TO LAYOUT. |
| | H) CORRIDOR ARCH SECTION DISPLAYS |
| | 6'- 8" HEIGHT. PLEASE VERIFY WITH |
| | BUILDING OFFICIALS IF THIS IS |
| | ACCEPTABLE. |
| | I) DOES UNIT A-2, UNIT C HAVE PIPE |
| | CHASES. |
| | J) THE PLAN REVIEW RESPONSE ITEM 20 |
| | SHOULD BE AN ALERT TONE, FOLLOWED BY |
| | "AN EMERGENCY HAS BEEN REPORTED IN THE |
| | BUILDING, PLEASE LEAVE THE BUILDING, |
| | VIA THE EXITS, DO NOT USE THE ELEVATORS |
| | FOLLOWED AGAIN BY THE ALERT TONE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |