| 2002-03-07 00:00:00 | ****************** UNSAT ************* |
| | |
| | PLEASE NOTE THERE WERE ONLY TWO NOTES, |
| | THAT STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE FIRE REVIEW COMMENTS, THERE |
| | MAY BE SOME CHANGES THEY MAY AFFECT |
| | ELECTRICAL DRAWINGS. |
| | PLEASE NOTE THAT THE FIRE DEPT AND |
| | ELECTRICAL NEED TO HAVE LAYOUT CHANGED |
| | FOR "FIRE DEPT RM`S". PLEASE NOTE THAT |
| | ROOMS SEEM TO BE TOO SMALL FOR OPERATION |
| | OF EQUIPMENT/PANELS DURING A FIREOR |
| | TESTING OF EQUIPMENT. PLEASE NOTE HOW |
| | DOOR(S) OPEN DIRECTLY INFRONT OF ONE OF |
| | THE PANELS. THIS WOULD MAKE IT DIFFICULT |
| | FOR CLEARENCES. PLEASE NOTE CLEARENCES |
| | PER 110-26. |
| | |
| | 1)NOTE: PLEASE NOTE FROM NOTE#16 FROM |
| | FIRST REVIEW. PLEASE NOTE THAT THE |
| | CONDUCTORS SIZES ARE NOW SHOWN FOR |
| | PANEL "DH". IT IS NOTED THAT OCP AT |
| | PANEL IS AT 500A`S. PLEASE CLARIFY LOAD |
| | BEING SHOWN AT 514AMPS? PLEASE NOTE |
| | 310-16 75 DEGREE COLUMN FOR SIZING. |
| | LOAD EXCEEDS RATING FOR TWO SETS OF |
| | 250MCM. (510A`S). |
| | |
| | 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR |
| | FIRE PUMP IS SHOWN AT 73.0 KVA.? THIS |
| | PUTS LOAD AT 202A. 430-150 PUTS MOTOR |
| | AT 211AMPS. |
| | |
| | PLEASE ALSO CLARIFY HOW LOAD SHOWN FOR |
| | PANEL"DE" IS SHOWN AT 124.6 KVA AND THEN |
| | ON LOAD STUDY FOR GEN., IT IS SHOWN AT |
| | 106.2? IT IS NOTED THAT NOTE MENTIONS |
| | ONLY "ONE ELEVATOR". PLEASE CLARIFY |
| | HOW LOAD DECREASES WHEN "ATS" IS FEEDING |
| | ENTIRE PANEL? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |