| 2001-10-20 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | CODE REFERENCE,STD PLUMBING CODE 94 |
| | (1)SHT A20,NOTE 7,FACBC-97 NOT APPROVED |
| | COMPLY WITH FAIR HOUSING ACT 24 CODE OF |
| | REGULATION (CFR) 100.205 (C)(IV), |
| | REVISED APRIL 1998, DESIGN MANUAL. |
| | REQUIRMENTS 1 THRU 7,SPECIFY OPTION "A" |
| | OR "B". SHOW MANEUVERING AND CLEAR FLOOR |
| | SPACE, REQUIRMENT 7 AND REINFORCED WALL |
| | AREAS, AS OUT LINED IN DESIGN MANUAL. |
| | (2) SHT A28 DETAIL 4,PROVIDE A ISOMETRIC |
| | DRAWING OF ROOF DRAINAGE WITH PIPE SIZES |
| | , SQUARE FOOTAGE; ALSO INCLUDE 1/2 THE |
| | VERTIAL WALLS AND UPPER ROOFS. |
| | PROVIDE CALCULATIONS FOR THE SECONDARY |
| | DRAINAGE, INCLUDE 1/2 THE VERTIAL WALLS |
| | AND UPPER ROOFS. SEC 1108,1108.3,1109. |
| | (3A)SHT P1 PROVIDE A COMPLETE PLAN VIEW |
| | OF THE UNDER GROUND STORM AND SANITARY |
| | BUILDING DRAINAGE SYSTEM,SHOW PIPE SIZES |
| | AND THE LOAD ON EACH SYSTEM, SEC 104.3 |
| | (B) TRASH ROOM DRAIN NOT APPROVED TO |
| | STORM DRAINAGE. SEC 701.5 |
| | (C) SANITARY BUILDING DRAINS, 4" THRU 6" |
| | CLEANOUTS NOT MORE THAN 80 FT INTERVALS. |
| | SEC 710.2.4 (2) |
| | (4) SHT P6 SPECIFY TYPE OF SHOCK |
| | ARRESTOR AND TABLE FOR SIZING, SEC 104.3 |
| | (5) SHT P 12 NOTE #10 RELIEF VENT, SHOW |
| | VENTS ON RISER,SHTS P8,P9. SEC 104.3 AND |
| | SEC 916. |
| | END OF COMMENTS PAUL SCHMITZ |
| | QUESTIONS 561-659-8096X 8233 |