| Date |
Text |
| 2001-10-09 00:00:00 | 1) SITE PLAN DOES NOT INDICATE FIRE |
| | HYDRANT LOCATIONS. |
| | 2) A DETERMINATION WILL BE REQUIRED BY |
| | THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WITH REGARDS TO THE COVERED WALKWAY. |
| | FS 553.895 (2) EXEMPTS AN OPEN PARKING |
| | GARAGE WITH A 20 FOOT SEPARATION FROM |
| | BEING FIRE SPRINKLER PROTECTED. THE |
| | COVERED PEDESTRIAN WALKWAY APPEARS TO |
| | CONNECT BOTH THE PARKING GARAGE AND THE |
| | HIGH-RISE BUILDING. |
| | 3) A KNOX-BOX WILL BE REQUIRED FOR FIRE |
| | ACCESS. |
| | 4) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 5) PLEASE CLARIFY WELL COMPACTED FIELD |
| | FOR FIRE TRUCK ACCESS. |
| | 6) A TEMPORARY STANDPIPE SYSTEM WILL |
| | BE REQUIRED WHEN CONSTRUCTION REACHES |
| | THREE STORIES AND FIFTY FEET. |
| | 7) STAIRS ARE TO BE CONTINIOUS WITH |
| | CONSTRUCTION. |
| | 8) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | THE STETCHER REQUIREMENTS OF 1997 |
| | STANDARD BUILDING CODE. |
| | 9) PLEASE EXPLAIN HOW ALL OF THE |
| | REQUIRED DEVICES FOR THE FIRE COMMAND |
| | CENTER ARE GOING TO FIT INTO THE |
| | CLOSET PROVIDED. PLEASE SEE 1997 |
| | STANDARD BUILDING CODE. |
| | 10) PLEASE DEMONSTRATE COMPLIANCE FOR |
| | SMOKE CONTROL REQUIREMENTS OF 1997 |
| | STANDARD BUILDING CODE. |
| | 11) SIGNS ARE REQUIRED FOR STAIRWAYS |
| | INDICATING FLOOR LEVEL, TERMINUS TOP |
| | AND BOTTOMS AND THE IDENTITY OF THE |
| | STAIRS. |
| | 12) PLEASE INDICATE WHAT PROVISIONS |
| | HAVE BEEN MADE FOR FIRE RESCUE ACCESS |
| | FOR THE NORTH AND SOUTH GATES. WILL |
| | THESE GATES BE ELECTRIC OR MANUALLY |
| | OPERATED. IF ELECTRIC IS BATTERY |
| | BACK-UP AVAILABLE. SEPARATE PLANS |
| | AND PERMITS REQUIRED FOR SECURITY GATES. |
| | 13) SITE PLAN DOES NOT INDICATE THE |
| | LOCATION OF THE ABOVEGROUND FUEL TANK |
| | SHOWN ON PAGE P-12. |
| | 14) NO FIRE DEPARTMENT CONNECTIONS |
| | SHOWN ON FP-1. SINCE THE BUILDING IS |
| | CONSIDERED HIGH-RISE, TWO FIRE |
| | DEPARTMENT CONNECTIONS WILL BE REQUIRED. |
| | 15) AREA DIRECTLY NEXT TO ELECTRICAL |
| | ROOM DISPLAYS NO FIRE SPRINKLER |
| | PROTECTION. WHAT IS THIS AREA USED FOR. |
| | 16) INTERIOR FINISH INFORMATION |
| | REQUIRED FOR WALLS AND CEILINGS OF |
| | BUILDINGS. |
| | 17) PLEASE INDICATE THAT ATTIC SPACES |
| | WILL NOT BE USED FOR STORAGE. |
| | 18) HOW IS COMBUSTIBLE LINT REMOVED |
| | FROM THE DRYER EXHAUST RISERS. |
| | 19) NO SMOKE DETECTORS SHOWN IN |
| | SLEEPING ROOMS. |
| | 20) PLEASE INDICATE WHAT THE VOICE |
| | EVACUATION MESSAGE OF THE FIRE ALARM |
| | SYSTEM WILL SAY. |
| | 21) ELECTRICAL DRAWINGS APPEAR TO BE |
| | INCOMPLETE. |
| | 22) PLEASE PROVIDE MORE DETAILS ON |
| | SMOKE EVACUATION SYSTEM FOR THE STAIR |
| | TOWERS AND IDENTIFY THAT THESE SYSTEMS |
| | WILL BE ON EMERGENCY POWER. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |