| Date |
Text |
| 2001-10-24 00:00:00 | **************** UNSAT ***************** |
| | |
| | |
| | 1)NOTE: PLEASE NOTE THAT IN ORDER TO DO |
| | A COMPLETE PLAN REVIEW. PLANS NEED TO |
| | BE COMPLETE. GAZEBO IS MISSING,GENERATOR |
| | LOACTION, MISSING ELECTRICAL ROOM DETAIL |
| | -S FOR FLOOR WITH HOUSE PANELS? |
| | |
| | 2)NOTE: PLEASE NOTE TWO FLOORS SHOWING |
| | HOUSE PANELS 4E AND 4H? |
| | |
| | 3)NOTE: PLEASE NOTE THAT CIRCUIT LAYOUT |
| | ON LOWER CORNER OF E1-2 DOES NOT |
| | CORRELATE WITH E3-1? |
| | |
| | 4)NOTE: PLEASE NOTE MEANS OF BEING ABLE |
| | TO SHUT DOWN GENERATOR TO BE GROUPED |
| | WITH MAINS? 230-72, 230-76,230-79 |
| | |
| | 5)NOTE: PLEASE NOTE THAT FIRE PUMP ROOM |
| | IS SHOWN ON SECOND FLOOR, WHERE IS MAIN |
| | ELECTRICAL ROOM? |
| | |
| | 6)NOTE: PLEASE NOTE COMPLETE CONCRETE |
| | ENCASEMENT OF SERVICE ENTRANCE CONDUCTOR |
| | S, NO MORETHAN 8' OF UNPROTECTED CONDUCT |
| | -ORS INSIDE THE BLDG. PER LOCAL AMEND. |
| | 230-70A |
| | |
| | 7)NOTE: PLEASE NOTE PANEL "A" NOT |
| | COMPLETED. |
| | |
| | 8)NOTE: PLEASE NOTE NO OCP SHOWN FOR |
| | ALL MAINS FOR APT PANELS??? |
| | |
| | 9)NOTE: PLEASE NOTE, ON E3-2 RISER SHOWS |
| | 12H AND 12E AND YET E3-1 DOES NOT SHOW |
| | WHERE THESE ARE FED FROM? PANEL "DE" |
| | DOES NOT SHOW? |
| | |
| | 10)NOTE: PLEASE NOTE GROUNDING ELECTRODE |
| | CONDUCTOR SIZE PER 250-66 NEEDS TO BE |
| | SHOWN ON E3-3 |
| | |
| | PLEASE NOTE THAT THERE ARE MANY ITEMS |
| | ON E3-1 THAT NEED TO BE ADDRESSED. |
| | |
| | 11)NOTE: PLEASE NOTE NO OCP SHOWN FOR |
| | FIRE PUMP, FROM FIRE PUMP CONTROL PANEL, |
| | AND FIRE PUMP ATS. |
| | |
| | 12)NOTE: PLEASE NOTE CONDUCTOR TO FIRE |
| | PUMP ARE SHOWN AT 250MCM??, PLEASE SEE |
| | SIZING PER LOAD OF PUMP 430-150 AND |
| | CONDCUTOR SIZES PER 310-16. |
| | |
| | 13)NOTE: PLEASE NOTE OCP PER 695-4-B-1 |
| | |
| | 14)NOTE: PLEASE NOTE THAT OCP ON GENER- |
| | -ATOR IS SHOWN AT 500AMPS WITH 250MCM?? |
| | 310-16. |
| | |
| | 15)NOTE: PLEASE NOTE THAT CONDCUTOR SIZE |
| | FOR 400A ATS MAIN IS SHOWN AT 4/0? |
| | 310-16 FOR 400AMPS, ALSO 350MCM FROM |
| | ATS TO PANEL "DE" ON 400A OCP?? |
| | |
| | 16)NOTE: PLEASE NOTE THAT NO CONDCUTOR |
| | SIZE IS SHOWN COMING FROM FPL TO 600A |
| | PANEL"DH"??? |
| | |
| | 17)NOTE: PLEASE NOTE THAT THERE ARE NO |
| | VOLTAGES SHOWN FOR PANEL"DH" ON PANEL |
| | SCHEDULE. |
| | |
| | 18)NOTE:PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PANEL"DH" "DE" ETC |
| | |
| | 19)NOTE: PLEASE NOTE THAT THERE ARE NO |
| | PANEL SCHEDULES SUBMITTED FOR ALL HOUSE |
| | PANELS, NOT TO INCLUDE CIRCUIT SCHEDULE |
| | ON E1-2. |
| | |
| | 21)NOTE:PLEASE NOTE THAT THE GENERATOR |
| | IS TO BE SIZED PER 695-B-1. PLEASE |
| | NOTE THAT LOAD EXCEEDS RATING OF GEN. |
| | PLEASE CLARIFY HOW AUTOMATIC SHEDDING |
| | OF LOADS WILL TAKE PLACE??? |
| | |
| | 22)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | COLOR CODING OF FEDDERS PER LOCAL |
| | AMENDMENTS 215-8 277/480V BR/PURP/YELLOW |
| | GRAY, 120/208 BLK/RED/BLUE. |
| | |
| | 23)NOTE: PLEASE CLARIFY GROUNDING SIZE |
| | OF CONDCUCTOR FOR GENERATOR AS #4,??? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. PLEASE CALL TO SET UP A |
| | MEETING IN PERSON TO CLARIFY ITEMS THAT |
| | MAY BE MORE CLEAR IN PERSON. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |