| 2001-11-08 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY. |
| | |
| | THE SOIL REPORT IS REQUIRED TO HAVE THE |
| | EMBOSSED SEAL OF THE ENGINEER TOGETHER |
| | WITH THE ORIGINAL SIGNATURE AND DATE. |
| | THIS IS REQUIRED FOR ALL DOCUMENTS |
| | PREPARED BY AN ENGINEER OR ARCHITECT |
| | AND SUBMITTED FOR PUBLIC RECORD.SEE |
| | FS 471 AND 481 |
| | |
| | PLEASE PROVIDE THE FIRE DESIGN NUMBERS |
| | FOR THE MASONRY WALLS SERVING AS SHAFT |
| | ENCLOSURES AND EXTERIOR WALLS.SEE SBC |
| | 701.5. |
| | |
| | WHAT IS THE MEANING OF THE NOTE ON |
| | SHEETA0-1 "ADJACENT BUILDING WALL |
| | CONSTRUCTED AS FIRE WALL AS DEFINED BY |
| | CODE." ? |
| | |
| | THE DOORS TO THE CLUBHOUSE AND FITNESS |
| | ROOMS SHOWN AS #26 ARE REQUIRED TO BE |
| | FIRE RATED.SEE SBC 705.1.2 AND |
| | 704.1.1. |
| | |
| | |
| | SBC 1008 REQUIRES ONE OF THE EXIT STAIRS |
| | TO BE CONTINUOUS TO THE ROOF. |
| | |
| | SBC 3104.3 REQUIRES "PROTECTION AT THE |
| | INTERFACE" WHERE THE COVERED WALKWAY |
| | JOINS THE BUILDING. |
| | |
| | NEITHER THE PLANS NOR THE SPECIFICATIONS |
| | INDICATE THE USE OF FIRE RETARDANT |
| | TREATED, (FRT) BLOCKING AS PROVIDED FOR |
| | IN SBC 609 AND SBC 707.1. |
| | |
| | SBC 104.2.1 DOES NOT ALLOW CITING THE |
| | CODE IN LIEU OF SPECIFIC DESIGN |
| | INFORMATION SUCH AS THAT FOUND ON SHEET |
| | A-29 "ADHERE DYPLAST W/ STANDARD |
| | BUILDING CODE 1403.6.8 ..."WHICH IS |
| | NOT A VALID CODE SECTION ANYWAY, PLEASE |
| | REVISE AS NECESSARY. |
| | |
| | DETAIL 1/A12 ON SHEET A29. SHOW A |
| | SPECIFIC CONNECTION DETAIL FOR THE |
| | STONE CORBEL OR IF DESIGN IS |
| | DESIGNATED, THE LOCATION, NATURE, |
| | DIRECTION AND MAGNITUDE OF THE FORCES |
| | TO BE RESISTED. |
| | |
| | MOST OF THE PAGES IN THE STRUCTURAL |
| | CALCULATIONS DO NOT PERTAIN TO THIS |
| | BUILDING.PLEASE PROVIDE COMPLETE |
| | CALCULATIONS DEMONSTRATING COMPLIANCE |
| | WITH SBC 1601 AND NOT JUST A WIND |
| | RESISTANCE INVESTIGATION. |
| | |
| | SHEET S-1.1 NOTE #8, WHAT IS THE TOP OF |
| | FOOTING ELEVATIONS? |
| | |
| | SEE SBC 1608.2.2 FOR THE GUARDRAIL |
| | DESIGN LOADS SHOWN ON SHEET A27 IN |
| | DETAIL 5/A25. |
| | |
| | SHEET S 1-1 DEPICTS COLUMNS NUMBERED 1 |
| | THROUGH 48 AND THE COLUMN SCHEDULE ON |
| | SHEET S 4-1 LISTS ONLY 42.THERE IS NO |
| | DETAIL FOR COLUMN #46. |
| | |
| | A THRESHOLD INSPECTION PLAN IS REQUIRED |
| | FOR THIS BUILDING AS PROVIDED FOR IN FS |
| | 553.71. |
| | |
| | SEVERAL AREAS OF THE SPECIFICATIONS |
| | ERRONEOUSLY CITE A 110 MPH WIND SPEED. |
| | PLEASE REVISE AS NECESSARY AND INCLUDE |
| | A SKETCH OF THE BUILDING DEFINING THE |
| | PRESSURE ZONES AND THEIR ATTENDANT |
| | PRESSURES. |
| | |
| | SMOKE DETECTORS ARE NOT SHOWN INSIDE OF |
| | THE SLEEPING ROOMS AS PROVIDE FOR IN |
| | NFPA 72 WHICH IS INVOKED BY SBC 905.2. |
| | |
| | THE STAIR SECTIONS SHOWN WITH RISER |
| | HEIGHTS OF 6.5" OR LESS WHEN TAKEN |
| | TOGETHER WITH THE DECLARED 11" TREAD DO |
| | NOT MEET THE 24"- 25" OF SBC 1007.3.1. |
| | SEE ALSO NFPA 101 FOR THE 7/11 |
| | REQUIREMENT. |
| | |
| | PLEASE PROVIDE CALCULATIONS AND A |
| | WRITTEN NARRATIVE TO BETTER DESCRIBE |
| | THE SEQUENCE OF OPERATIONS FOR SMOKE |
| | CONTROL DECLARED ON SHEET M-8. |
| | DEMONSTRATE THAT THE BAROMETRIC RELIEF |
| | DAMPER WILL PROVIDE FOR AT LEAST 2500 |
| | CFM FLOWINGAND ANTICPATED STACK |
| | PRESSURES IN THE BUILDING.SEE SBC |
| | 412.11 (5). |
| | |
| | DESCRIBE HOW SMOKE REMOVAL FROM THE |
| | CORRIDORS WILL BE ACCOMPLISHED AT A |
| | RATE OF AT LEAST 6 AIR CHANGES PER |
| | HOUR. SEE SBC 412.5 (3) IF THIS IS THE |
| | INTENDED METHOD. |
| | |
| | SHEET E3-5 DOES NOT SHOW THE FIRE |
| | DEPARTMENT COMMUNICATION SYSTEM |
| | REQUIRED BY SBC 412.3.3.ARE THE MARKS |
| | SHOWN ON THE PLANS AS [T] THE INTENDED |
| | LOCATIONS? |
| | |
| | E 3-5, OR THE SPECIFICATIONS, DO NOT |
| | SHOW THE BACKUP POWER SUPPLY FOR THE |
| | ALARM SYSTEM. ELEVATOR RECALL BY |
| | ELEVATOR LOBBY SMOKE DETECTOR IS NOT |
| | NOTED IN THE SEQUENCE OF OPERATION. SEE |
| | SBC 412.6.3. |
| | |
| | THERE IS NO SPECIFICATION FOR THE |
| | GENERATOR FUEL SUPPLY.SEE SBC |
| | 412.7.1.2.ALSO THE E SHEETS DO NOT |
| | CLEARLY INDICATE THE MANDATORY STAND BY |
| | POWER LOADS TO BE CARRIED BY THE |
| | GENERATOR.SEE SBC 412.7.2. |
| | |
| | SEVERAL OF THE DOORS WITHIN THE UNITS DO |
| | NOT MEET THE NOMINAL 32" WIDTH REQUIRED |
| | BY THE FAIR HOUSING ACT. TOILET AND |
| | POWDER ROOMS, BEDROOMS, WALKIN CLOSETS, |
| | PATIOS, AND SIMILAR LIVING AREAS AS |
| | CITED IN THAT LAW.PLEASE REVISE AS |
| | NECESSARY. |
| | |
| | THE METRO DADE NOTICE OF ACCEPTANCE |
| | REPORT #990212.09 IS ILLEGIBLE. |
| | |
| | NOA #97-1204.02 IS EXPIRED. |
| | |
| | 00-0721.05 FOR THE SHUTTERS DOES NOT |
| | HAVE THE COMPONENTS SELECTED OR THE |
| | LOCATION OF THEIR PROPOSED APPLICATION |
| | ON THE BUILDING.SHUTTERS ON |
| | MULTI-STORY BUILDINGS IN LIEU OF IMPACT |
| | RESISTANT GLAZING, ARE SUBJECT TO |
| | APPROVAL BY THE BUILDING OFFICIAL ON A |
| | CASE BY CASE BASIS. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO THE |
| | COUNTY FOR THE CITY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE,AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |