Plan Review Notes
Plan Review Notes For Permit 01091467
Permit Number 01091467
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-22 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES PER SPC TABLE 407. EXIST-
 ING HDCP TOILET ROOM DOES NOT MEET CODE.
 2) GREASE TRAP TO BE SIZED AND LOCATED
 BY UTILITY DEPT REG. SEWER TREATMENT
 DEPT. PLEASE CONTACT RODNEY COMPO (561)
 837-4074. WASTE ORD. 2938-96
 3) PAGE P-1 NO DRY HORIZONTAL VENTS FOR
 SANT. SPC SEC 906.2.1
 4) PAGE P-1/P-2 3 COMPARTMENT SINK TO
 DRAIN INDIRECTLY TO A FLOOR SINK. SPC
 SEC 804.1
 5) PAGE P-2 SEPARATE PERMIT FOR GAS RE-
 QUIRED. SEE ATTACHED SHEET FOR PERMIT
 APPLICATION REQUIREMENTS. PLEASE SUBMIT
 INFORMATION AT TIME OF PERMIT APPLICAT-
 ION.
 6) PAGE P-2 WATER HEATER DETAIL. T & P
 VALVE DISCHARGE FULL SIZE, & PAN DRAIN
 LINE (1") SHALL RUN OUTSIDE TO 6" ABOVE
 GRADE OR TO A FLOOR SINK WITH TRAP PRIM-
 ER.
 7) PAGE P-2 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED PER
 MANUFACTURE INSTALLATION INSTRUCTIONS &
 WH-PDI 201. THEY SHALL BE IN AN EFFECT-
 IVE RANGE OF THE FIXTURE.
  
 REVIEW BY KEN STEVENS