| Plan Review Notes For Permit 01091467 |
| Permit Number |
01091467 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLEASE SUBMIT CALCULATIONS FOR MINI- | | | MUM FACILITIES PER SPC TABLE 407. EXIST- | | | ING HDCP TOILET ROOM DOES NOT MEET CODE. | | | 2) GREASE TRAP TO BE SIZED AND LOCATED | | | BY UTILITY DEPT REG. SEWER TREATMENT | | | DEPT. PLEASE CONTACT RODNEY COMPO (561) | | | 837-4074. WASTE ORD. 2938-96 | | | 3) PAGE P-1 NO DRY HORIZONTAL VENTS FOR | | | SANT. SPC SEC 906.2.1 | | | 4) PAGE P-1/P-2 3 COMPARTMENT SINK TO | | | DRAIN INDIRECTLY TO A FLOOR SINK. SPC | | | SEC 804.1 | | | 5) PAGE P-2 SEPARATE PERMIT FOR GAS RE- | | | QUIRED. SEE ATTACHED SHEET FOR PERMIT | | | APPLICATION REQUIREMENTS. PLEASE SUBMIT | | | INFORMATION AT TIME OF PERMIT APPLICAT- | | | ION. | | | 6) PAGE P-2 WATER HEATER DETAIL. T & P | | | VALVE DISCHARGE FULL SIZE, & PAN DRAIN | | | LINE (1") SHALL RUN OUTSIDE TO 6" ABOVE | | | GRADE OR TO A FLOOR SINK WITH TRAP PRIM- | | | ER. | | | 7) PAGE P-2 WATER RISER DIAGRAM. WATER | | | HAMMER ARRESTORS SHALL BE INSTALLED PER | | | MANUFACTURE INSTALLATION INSTRUCTIONS & | | | WH-PDI 201. THEY SHALL BE IN AN EFFECT- | | | IVE RANGE OF THE FIXTURE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|