| Notes |
| Date |
Text |
| 2001-10-01 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | FOR OFFICE/STORAGE AREAS NEED TO MEET | | | LOCAL AMENDMENTS,210-50. PLEASE SEE | | | STORAGE AREAS UPSTAIRS. | | | | | | 2)NOTE: PLEASE INCLUDE FEEDS/GOING TO | | | EXISTING PANELS ON RISER DIAGRAM. | | | | | | 3)NOTE: PLEASE NOTE THAT EXISTING PANELS | | | ARE SHOWN IN NEW ELECTRICAL ROOM AND | | | NEW PANELS GOING INTO OFFICE AREA.PLEASE | | | PLACE NOTE ON PLANS (E-1) THAT AREA | | | INFRONT OF NEW ELECTRICAL EQUIPMENT TO | | | BE LABELED AND REMAIN DEDICATED | | | ELECTRICAL SPACE PER 110-26. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE AREANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|