| 2002-03-14 00:00:00 | ****************** UNSAT ************** |
| | |
| | PLEASE NOTE THAT NOT ALL NOTES FROM |
| | FIRST REVIEW WERE ADDRESSED. |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | SEE NFPA-72 2-5-2.1.3 |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | PLEASE NOTE, NO PANEL SCHEDULE SUBMITTED |
| | OR LOAD CALCULATIONS.220-3-C-1/215-5 |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | STILL MISSING IN MANY LOCATIONS. |
| | PLEASE CLARFIY"FIXTURES"? SHOWN ON 3RD |
| | FLOOR LEVEL. LIGHTS? HOW ARE THEY |
| | CONTROLLED? |
| | |
| | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 5) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | PLEASE CLARIFY FOR AHU#2 SHOWN ABOVE |
| | BATH ROOM? |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7)NOTE: PLEASE NOTE KITCHENCOUNTERTOP |
| | RECEPT SPACING FOR PENINSULAR.PLEASE |
| | SEE 210-52-C-3 AND 4. |
| | |
| | 8) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | MISSING IN BOTH SMALL BATHS DOWNSTAIRS. |
| | PLEASE NOTE GFI IN SM.BATH 210-8. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |