| 2001-10-19 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 5) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | 7) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 8)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | HALLWAY(S) 210-52H |
| | |
| | 9)NOTE: PLEASE NOTE MISSING DISCONNECT |
| | FORA/C CU 440-11 |
| | |
| | 10)NOTE: PLEASE SHOW ALL BATHS AS GFI/ |
| | GFI PROTECTED. 210-8 |
| | |
| | 11)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | BATH(S) PER 210-52D |
| | |
| | 12)NOTE: PLEASE NOTE MISSING OUTLETS |
| | FOR KITCHEN COUNTERSPACE PER 210-52-C-3 |
| | |
| | 13)NOTE: PLEASE NOTE MISSING MEANS OF |
| | EGRESS LIGHTING FOR STAIRS? 210-70 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |