| Plan Review Notes For Permit 01091396 |
| Permit Number |
01091396 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-02 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) FIRE-ALARM NOTES ON PAGE FAO.1 | | | INDICATES CLASS B, STYLE C CIRCUITS. | | | ONLY CLASS A, STYLE D CIRCUITS ALLOWED. | | | 3) FIRE ALARM NOTES INDICATES DUCT | | | SMOKE DETECTOR WHEN ACTIVATED WILL | | | CAUSE A TROUBLE SIGNAL. WHEN ACTIVATED | | | THIS DEVICE IS TO SOUND FIRE ALARM | | | SYSTEM. | | | 4) ARE ANY STORAGE RACKS PLANNED FOR | | | THE WAREHOUSE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|