2002-08-29 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT AM-61 HDCP W/C DETAIL SHOWS 19"-
 20", PER SEC 4.16.3 THE HEIGHT OF WATER
 CLOSETS SHALL BE 17" TO 19" MEASURED
 FROM THE TOP OF THE TOILET SEAT. (FIG.
 29(B). ALSO SEE DETAIL ON SHT AMP-61.
 PLEASE CHANGE DETAILS.
 2) SHT AMP-61 SANITARY RISER DIAGRAM, A
 2-WAY CLEANOUT IS REQUIRED WHERE THE
 SLOP SINK EXITS THE BLDG NEAR THE JUNCT-
 ION OF THE BLDG DRAIN & SEWER.
 3) SHT AMP-61 DOMESTIC WATER RISER DIA-
 GRAM, AIR CHAMBERS ARE A QUICK FIX AND
 REQUIRE AN ACCESS PANEL AND SHALL BE
 PROVIDED WITH AN ACCESSIBLE MEANS FOR
 RESTORING THE AIR. APPROVED WATER HAMMER
 ARRESTORS DO NOT REQUIRE EITHER ACCESS
 OR SERVICE. IF W.H.A'S ARE USED THEY
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROPS AS SHOWN FOR AIR CHAMBERS.
 4) WATER HEATER SHALL HAVE A SHIPS LADD-
 ER AND A WORKING PLATFORM INSTALLED TO
 MAKE THE WATER HEATER READILY ACCESSIBLE
 OR PUT WATER HEATER ON FLOOR.
 5) IF THE WATER HEATER IS INSTALLED ON
 THE PLATFORM THEN A PAN IS REQUIRED WITH
 A 1" PAN DRAIN. PLEASE SUBMIT DETAILS.
  
 REVIEW BY KEN STEVENS