Plan Review Notes
Plan Review Notes For Permit 01091384
Permit Number 01091384
Review Stop M
Sequence Number 2
Notes
Date Text
2002-08-21 00:00:00PROVISO:
  
 PLAN SHEET AC-U3 INDICATES TOILET EXHAUS
 T PENETRATING WHAT APPEARS TO BE A RATED
 WALL (BREEZWAY).THIS IS NOT ACCEPTABL
 E.EXHAUST CAN ONLY TERMINATE TO THE EX
 TERIOR WALL AT THE END OF THE BUILDING.
  
 PLAN SHEET AC-D1 DETAIL FOR THE AHU REMO
 VES THE VIBRATION ISOLATION.