| 2002-08-21 00:00:00 | PROVISO: | | | | | | PLAN SHEET AC-U3 INDICATES TOILET EXHAUS | | | T PENETRATING WHAT APPEARS TO BE A RATED | | | WALL (BREEZWAY).THIS IS NOT ACCEPTABL | | | E.EXHAUST CAN ONLY TERMINATE TO THE EX | | | TERIOR WALL AT THE END OF THE BUILDING. | | | | | | PLAN SHEET AC-D1 DETAIL FOR THE AHU REMO | | | VES THE VIBRATION ISOLATION. |
|