Plan Review Notes For Permit 01091382
Permit Number 01091382
Review Stop P
Sequence Number 2
Notes
Date Text
2002-08-06 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT AM-1 DRINKING FOUNTAIN, IF A HI/
 LOW DRINKING FOUNTAIN IS NOT USED, PRO-
 VISIONS SHALL BE MADE FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION
 4.1.3(10)(A).
 2) SHT AM-2 ELECTRIC WATER HEATER SHALL
 BE READILY ACCESSIBLE PER SEC 501.7.
 PLEASE SHOW DETAIL
 3) SHT AM-P1 WATER HEATER NOTES: #4
 MENTIONS AN EMERGENCY PAN, BUT ITS NOT
 SHOWN ON W/HEATER DETAIL. PLEASE CLAIRFY
 4) SHT AM-P1 PLUMBING GENERAL NOTES:
 A) #3 - 2-1/2" AND SMALLER PIPE TO BE
 SLOPED AT A MINIMUM OF 1/4" PER FOOT.
 SECTION 705.2
 B) #6 DIELECTRIC UNIONS NOT APPROVED
 FOR WATER PIPE. - DELETE REFERENCE OR
 CHANGE TO DIELECTRIC COUPLINGS.
 C) #11 AIR CHAMBERS ARE A QUICK FIX. IF
 USED, AN ACCESS PANEL AND MEANS TO RECH-
 ARGE SHALL BE REQUIRED. SECTION 607.8.3
 WATER HAMMER ARRESTORS SHOULD BE USED &
 LOCATED NEAR THE FIXTURES IN AN "EFFICT-
 IVE RANGE" NOT AT THE TOP OF DROPS.
 5) REVISION - NO DEAD ENDS ALLOWED ON
 SANITARY. (SEE UPSTREAM END OF BLDG
 DRAIN)
  
 REVIEW BY KEN STEVENS