| 2001-10-09 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT NO LOAD CALCS/ |
| | PANEL SCHEDULES/ RISER DIAGRAMS ETC |
| | WERE SUBMITTED? 220-3-C1/215-5 310-16,, |
| | ,,, |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE SHOW SWITCHING OF EGRESS LIGHTING |
| | FOR STAIRWAY.? |
| | ELECTRICAL PLANS NEED TO SHOW STAIRS |
| | |
| | 5)NOTE: PLEASE SHOW SINKL LOCATIONS FOR |
| | BATHS SO OUTLET LOCATIONS MEET 210-52D |
| | |
| | 6)NOTE: PLEASE NOTE DEDICATED |
| | ELECTRICALSPACE FOR PANEL SHOWN IN |
| | STORAGE ROOM |
| | IN A SF RESIDENCE. ALSO SEE 384-7 |
| | IGNITIBLE MATERIALS. |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | CLARIFY SPACING IN "NEW GUEST BR" |
| | ALSO EGRESS LIGHTING? 210-70 |
| | |
| | 8)NOTE: PLEASE NOTE MISSING NEW CU FOR |
| | A/C ON ELECTRICAL PLAN WITH DISCONNECTS |
| | PER 440-11 |
| | |
| | 9) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 10)NOTE: PLEASE NOTE EGRESS FROM BATH |
| | TO OUTSIDE W/ NO EGRESS LIGHTING |
| | CONTROL-S? 210-70 |
| | |
| | 11)NOTE: PLEASE NOTE CIRCUITS BEING |
| | SHOWN FOR DRYER AND WATER HEATER IN |
| | LAUNDRY ROOM BUT NOT FOR WASHER? PER |
| | 210-52-F. PLEASE CLARFIY-EXISTING IN |
| | OTHER LOCATION? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |