| 2001-10-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01091365 |
| | 300 34TH ST |
| | CONT: WAYNE HETZEL BUILDING |
| | PHONE: (561) 881-2108 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS TO STANDARD BUILDING |
| | CODE |
| | 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | A)- WINDOWS INDICATE WHICH KDI WINDOW |
| | SYSTEM THAT YOU ARE USING? ONLY THE |
| | KDI 2000 WINDOW SYSTEM IS TESTED |
| | FOR LARGE MISSLE IMPACT TESTING! |
| | IF A KDI WINDOW SYSTEM OTHER THAN |
| | THE "2000" SERIESIS INSTALLED, |
| | STORM SHUTTERS WILL BE REQUIRED. |
| | B)- OUT SWING FRENCH DOORS; WILL RE- |
| | QUIRE STORM SHUTTERS. |
| | C)- IN SWING FRENCH DOORS; NEW REPORT |
| | REQUIRED, EXPIRED |
| | D)- SKYLIGHT: MISSING PRODUCT APPROVAL |
| | REPORT, GLAZED OPENING WILL REQUIRE |
| | LARGE MISSLE IMPACT RESISTANCE TEST |
| | ING OR STORM SHUTTERS. |
| | E)- STORM SHUTTERS: A KEY DIAGRAPM & |
| | INSTALLATION SCHEDULE IS ALSO RE- |
| | QUIRED, A SAMPLE IS ATTACHED. |
| | |
| | 2)- STAIRS: WINDERS, SBC 1007.8.1. |
| | A MINIMUM TREAD DEPTH OF 6" AT THE |
| | NARROW EDGE & SHALL HAVE A MINIMUM |
| | TREAD DEPTH OF 11" AT A POINT 12" |
| | FROM THE NARROW EDGE. |
| | |
| | 3)-SHEET A511 (DETAIL 1) : |
| | A)- CEILING LINE/ TRUSS LINE MISSING |
| | FIRE BLOCKING |
| | B)- 2ND FLOOR WOOD NAILER AT BEAM, |
| | REQUIRED TO BE PRESSURE TREATED |
| | |
| | 4)- SHEET A511 (DETAIL 3) : |
| | A)- CAANTILEVERED BALCANY- THE BEAM IN- |
| | DICATES THE SIZE OF THE STEEL, BUT |
| | NOT THE SIZE OR FREQUENCY OF HOOPS & |
| | STIRRUPS. |
| | B)- GAURDRAIL TO COMPLY WITH 1015.3, |
| | OPENINGS 4" |
| | C)- MISSING FIRE STOPPING CEILING LEVEL |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096X 8412 |