| Plan Review Notes For Permit 01091364 |
| Permit Number |
01091364 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT 01091364 | | | 6199-6225 EATON ST. | | | | | | TRUSS PLANS: PROVISO | | | ARCH SHEET 10, WOOD TO WOOD STRAP | | | SCHEDULE. WOOD STRAP SCHEDULE INDICATES | | | A WA-1, WA-2 & WA-3. PLANS INDICATE A | | | WA-4 & WA-5 WHICH ARE MISSING FROM THE | | | SCHEDULE. PROVIDE ADDITIONAL INFORMATION | | | FOR TIE DOWN SCHEDULE. | | | | | | THE SECOND ISSUE THE RIVOT TRUSS ANCHOR | | | SSCHEDULEA-2 INDICATE THE USE OF (2) | | | TAPL 16 ANCHORS ON A DOUBLE MEMBER TRUSS | | | THE MANUFACTURE INDICATE THAT THEY ARE | | | NOT TO BE PLACED CLOSER THAN 8" O.C. | | | WHEN USED CLOSER THAN 8"O.C. A DERATING | | | FACTOR OCCURS, SHALL REQUIRE WHAT THE | | | COMBINED LOAD SHALL BE? | | | | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | (561) 659_8096 X 8412 |
|