Plan Review Notes
Plan Review Notes For Permit 01091364
Permit Number 01091364
Review Stop M
Sequence Number 2
Notes
Date Text
2001-12-05 00:00:00 
  
 SPEC SHEET FOR DRYER DOES NOT ADDRESS
 EXHAUST DUCT.
  
 PLANS DO NOT REFLECT WHICH DRYER IS
 BEING INSTALLED (GAS OR ELECTRIC).
  
 PROVISO BY N. DENMARK (10-15-01):
  
 DRYER DUCTS LONGER THAN 25' INCLUDING 5'
 REDUCTION FOR EACH 90 AND 2 1/2' EACH
 45 DEGREE ANGLE REQUIRE MANUFACTURERS
 SPECIFICATION SHOWING ALLOWABLE LENGTH
 FOR THE DRYER TO BE USED.
  
 IF DRYERS ARE NOT TO BE INSTALLED AT
 TIME OF FINAL THE CODE MINIMUM WILL BE
 INFORCED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.