2001-12-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHTS A5.1 - A5.4, MINIMUM FACILITIES
 CALL FOR 2 DRINKING FOUNTAINS. HI/LOW
 DOES NOT CONSTITUTE 2 DRINKING FOUNTAINS
 BECAUSE IT IS JUST ONE FIXTURE AND TWO
 ARE REQUIRED. ONE MORE DRINKING FOUNTAIN
 IS REQUIRED PER SPC TABLE 407.
 2) SHT A5.4 DETAIL #1 ENLARGED FLOOR
 PLAN. CLEAR FLOOR SPACE FOR URNAL NOT
 SHOWN. HDCP SPACE FOR URNAL SHOWS 2'6"
 FROM WALL TO CENTER OF DIVIDER. 30" IS
 REQUIRED FOR CLEAR FLOOR SPACE.
 3) SHT M-2 PLUMBING NOTES #13. AIR CHAM-
 BERS REQUIRE ACCESS PANELS AND SHALL BE
 RECHARGEABLE PER SPC SEC 607.8.3. WATER
 HAMMER ARRESTORS ARE RECOMMENDED AND FOR
 APPROVED ARRESTORS NO ACCESS IS REQUIRED
 ALSO THE WATER HAMMER ARRESTORS SHALL BE
 SIZED AND LOCATED, (CLOSE TO FIXTURE IN
 AN EFFECTIVE RANGE - NOT AT TOP OF DROP
 AS SHOWN ON RISER DIAGRAM) PER MANUFACT-
 URE INSTALLATION INSTRUCTIONS AND WH-PDI
 201.
  