| Plan Review Notes For Permit 01091347 |
| Permit Number |
01091347 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-03 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHTS A5.1 - A5.4, MINIMUM FACILITIES | | | CALL FOR 2 DRINKING FOUNTAINS. HI/LOW | | | DOES NOT CONSTITUTE 2 DRINKING FOUNTAINS | | | BECAUSE IT IS JUST ONE FIXTURE AND TWO | | | ARE REQUIRED. ONE MORE DRINKING FOUNTAIN | | | IS REQUIRED PER SPC TABLE 407. | | | 2) SHT A5.4 DETAIL #1 ENLARGED FLOOR | | | PLAN. CLEAR FLOOR SPACE FOR URNAL NOT | | | SHOWN. HDCP SPACE FOR URNAL SHOWS 2'6" | | | FROM WALL TO CENTER OF DIVIDER. 30" IS | | | REQUIRED FOR CLEAR FLOOR SPACE. | | | 3) SHT M-2 PLUMBING NOTES #13. AIR CHAM- | | | BERS REQUIRE ACCESS PANELS AND SHALL BE | | | RECHARGEABLE PER SPC SEC 607.8.3. WATER | | | HAMMER ARRESTORS ARE RECOMMENDED AND FOR | | | APPROVED ARRESTORS NO ACCESS IS REQUIRED | | | ALSO THE WATER HAMMER ARRESTORS SHALL BE | | | SIZED AND LOCATED, (CLOSE TO FIXTURE IN | | | AN EFFECTIVE RANGE - NOT AT TOP OF DROP | | | AS SHOWN ON RISER DIAGRAM) PER MANUFACT- | | | URE INSTALLATION INSTRUCTIONS AND WH-PDI | | | 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|