| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | FROM FIRST REVIEW WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 215-5,220-10,220-3,220-10.220-11, | | | 220-13 ETC. | | | PLEASE NOTE ALL CONTINUOUS LOADS ARE TO | | | BE SHOWN AT 125%.215-2,3/ 230-42 | | | | | | 3)NOTE: PLEASE SHOW/CLARIFY GROUNDING | | | OF TRANSFORMER 250-30. | | | | | | 4)NOTE: PLEASE CLARIFY LOAD ON EXISTING | | | "MDP". PLANS SHOW ADDING A LARGE LOAD. | | | PLEASE SHOW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|