Plan Review Notes
Plan Review Notes For Permit 01091347
Permit Number 01091347
Review Stop E
Sequence Number 2
Notes
Date Text
2001-11-26 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 215-5,220-10,220-3,220-10.220-11,
 220-13 ETC.
 PLEASE NOTE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%.215-2,3/ 230-42
  
 3)NOTE: PLEASE SHOW/CLARIFY GROUNDING
 OF TRANSFORMER 250-30.
  
 4)NOTE: PLEASE CLARIFY LOAD ON EXISTING
 "MDP". PLANS SHOW ADDING A LARGE LOAD.
 PLEASE SHOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372