| Date |
Text |
| 2001-10-22 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) CALCULATIONS FOR MINIMUM FIXTURES PER |
| | SPC-94 TABLE 407 INDICATE MORE FIXTURES |
| | ARE REQUIRED. 271 PERSONS REQUIRE 6 MALE |
| | AND 6 FEMALE W/C'S REQUIRED. ALSO 2 |
| | DRINKING FOUNTAINS ARE REQUIRED. |
| | 2) PAGE A9.3, DETAIL #3 HDCP W/C TO BE |
| | 1'6" TO CENTER OF W/C OFF WALL AND HDCP |
| | LAV TO BE 2'10" AFF. PLEASE INDICATE |
| | THIS ON PLANS. |
| | 3) PAGE A9.3 DETAIL #6 & #9 HDCP W/C TO |
| | BE 1'6" OFF WALL TO CENTER OF W/C, AND |
| | LAV TO BE 2'10" AFF MAX. |
| | 4) PLEASE PROVIDE AN ARCHITECTUAL FLOOR |
| | PLAN FOR MENS & WOMENS BATHROOMS WITH |
| | ALL DEMENSIONS. SHOW CLEAR FLOOR SPACE |
| | FOR ALL HDCP FIXTURES AND SHOW DEMENS- |
| | IONS FOR ALL STALLS, AND URNAL STALLS. |
| | 5) PAGE M1, SANITARY RISER DIAGRAM RE- |
| | QUIRED. SHOW ALL PIPE SIZES. SHOW TIE-IN |
| | TO EXISTING SANT. AND VENT THRU ROOF OR |
| | TIE-IN TO EXISTING. |
| | 6) PAGE M1, WATER RISER DIAGRAM REQUIRED |
| | SHOW ALL PIPE SIZES AND LOCATION AND |
| | SIZE OF WATER HAMMER ARRESTORS. LOCATION |
| | SHALL BE BY MANUFACTURE INSTALLATION IN- |
| | STRUCTIONS AND WH-PDI 201. AIR CHAMBERS |
| | ARE A "QUICK FIX" AND SHOULD NOT BE USED |
| | BUT IF THEY ARE THEY SHALL COMPLY WITH |
| | SPC-94 607.8.3 AND BE ACCESSIBLE AND RE- |
| | CHARGEABLE. |
| | |