2001-10-22 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) CALCULATIONS FOR MINIMUM FIXTURES PER
 SPC-94 TABLE 407 INDICATE MORE FIXTURES
 ARE REQUIRED. 271 PERSONS REQUIRE 6 MALE
 AND 6 FEMALE W/C'S REQUIRED. ALSO 2
 DRINKING FOUNTAINS ARE REQUIRED.
 2) PAGE A9.3, DETAIL #3 HDCP W/C TO BE
 1'6" TO CENTER OF W/C OFF WALL AND HDCP
 LAV TO BE 2'10" AFF. PLEASE INDICATE
 THIS ON PLANS.
 3) PAGE A9.3 DETAIL #6 & #9 HDCP W/C TO
 BE 1'6" OFF WALL TO CENTER OF W/C, AND
 LAV TO BE 2'10" AFF MAX.
 4) PLEASE PROVIDE AN ARCHITECTUAL FLOOR
 PLAN FOR MENS & WOMENS BATHROOMS WITH
 ALL DEMENSIONS. SHOW CLEAR FLOOR SPACE
 FOR ALL HDCP FIXTURES AND SHOW DEMENS-
 IONS FOR ALL STALLS, AND URNAL STALLS.
 5) PAGE M1, SANITARY RISER DIAGRAM RE-
 QUIRED. SHOW ALL PIPE SIZES. SHOW TIE-IN
 TO EXISTING SANT. AND VENT THRU ROOF OR
 TIE-IN TO EXISTING.
 6) PAGE M1, WATER RISER DIAGRAM REQUIRED
 SHOW ALL PIPE SIZES AND LOCATION AND
 SIZE OF WATER HAMMER ARRESTORS. LOCATION
 SHALL BE BY MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND WH-PDI 201. AIR CHAMBERS
 ARE A "QUICK FIX" AND SHOULD NOT BE USED
 BUT IF THEY ARE THEY SHALL COMPLY WITH
 SPC-94 607.8.3 AND BE ACCESSIBLE AND RE-
 CHARGEABLE.
  