Plan Review Notes
Plan Review Notes For Permit 01091347
Permit Number 01091347
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-09-26 00:00:001) PLEASE INDICATE THE GRADE LEVELS
 PLANNED FOR THE FOURTH FLOOR.
 PLEASE BE ADVISED THAT CERTAIN
 RESTRICTIONS APPLY TO GRADE
 LEVELS ABOVE THE SECOND FLOOR.
 2) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM EQUIPMENT
 ADDITION.
 4) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 5) PANIC HARDWARE WILL BE REQUIRED SINCE
 CAPACITIES OF THE FOURTH FLOOR EXCEEDS
 100 PERSONS.
 6) NOTES SECTION INDICATES DUCT SMOKE
 DETECTORS WILL BE INSTALLED IN SUPPLY.
 NORMALLY DUCT SMOKE DETECTORS IN UNITS
 UNDER 2000 CFM ARE INSTALLED IN THE
 RETURNS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910