| Plan Review Notes For Permit 01091347 |
| Permit Number |
01091347 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-26 00:00:00 | 1) PLEASE INDICATE THE GRADE LEVELS | | | PLANNED FOR THE FOURTH FLOOR. | | | PLEASE BE ADVISED THAT CERTAIN | | | RESTRICTIONS APPLY TO GRADE | | | LEVELS ABOVE THE SECOND FLOOR. | | | 2) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM EQUIPMENT | | | ADDITION. | | | 4) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | 5) PANIC HARDWARE WILL BE REQUIRED SINCE | | | CAPACITIES OF THE FOURTH FLOOR EXCEEDS | | | 100 PERSONS. | | | 6) NOTES SECTION INDICATES DUCT SMOKE | | | DETECTORS WILL BE INSTALLED IN SUPPLY. | | | NORMALLY DUCT SMOKE DETECTORS IN UNITS | | | UNDER 2000 CFM ARE INSTALLED IN THE | | | RETURNS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|