| Notes |
| Date |
Text |
| 2001-10-01 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO RISER | | | DIAGRAM WAS SUBMITTED TO SHOW HOW THE | | | PANELS ARE BEING FED? WHERE,HOW,EXISTING | | | ???? | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED. PLEASE | | | NOTE THAT LOAD CALCS NEED TO BE SHOWN | | | PER 220. SQ FT ETC ETC. CONTINUOUS LOADS | | | KVA? ETC. | | | | | | 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | | ROOM SHOWS TRANSFORMER, BUT NOTHING | | | SHOWN ON A ONE-LINE DIAGRAM. | | | PLEASE SUBMIT A ONE-LINE WITH THE ABOVE | | | INFORMAITON FOR REVIEW. | | | | | | PLEASE SUBMIT FOR REVIEW ALL OF THE | | | ABOVE INFORMATION. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|