Plan Review Notes
Plan Review Notes For Permit 01091347
Permit Number 01091347
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-01 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO RISER
 DIAGRAM WAS SUBMITTED TO SHOW HOW THE
 PANELS ARE BEING FED? WHERE,HOW,EXISTING
 ????
  
 2)NOTE: PLEASE ALSO NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED. PLEASE
 NOTE THAT LOAD CALCS NEED TO BE SHOWN
 PER 220. SQ FT ETC ETC. CONTINUOUS LOADS
 KVA? ETC.
  
 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 ROOM SHOWS TRANSFORMER, BUT NOTHING
 SHOWN ON A ONE-LINE DIAGRAM.
 PLEASE SUBMIT A ONE-LINE WITH THE ABOVE
 INFORMAITON FOR REVIEW.
  
 PLEASE SUBMIT FOR REVIEW ALL OF THE
 ABOVE INFORMATION. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372