| Plan Review Notes For Permit 01091347 |
| Permit Number |
01091347 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-17 00:00:00 | THE TITLE SHEET CITES THE "LATEST | | | EDITION" OF THE STANDARD BUILDING CODE. | | | THE CITY AND STATE, CURRENTLY INVOKE | | | THE 1997 EDITION.PLEASE REVISE AND | | | ENSURE COMPLIANCE AS NECESSARY. | | | | | | SECTION 6/A8.5 SHOWS PT LUMBER.IT | | | SHOULD BE FRT.SEE SBC 609.2.1. | | | | | | SECTIONS 9 & 10/A8.5 HAVE A NOTE "FASTEN | | | TO STRUCTURE ABOVE".PROVIDE SPECIFIC | | | CONNECTION DETAILS.SEE SBC 104.2. | | | | | | SBCT705.1.2 REQUIRES DOORS #419A AND | | | #420A TO BE FIRE RATED. | | | | | | PLEASE PROVIDE A SEATING PLAN.SEE SBC | | | 1003.1.2. | | | | | | SHOW THE FIRE EXIT HARDWARE FOR THE | | | STAIR DOORS.SEE SBC 1021.2.1 | | | | | | NOTE THE GRADE FOR THESE CLASSROOMS AS | | | 3RD OR GREATER.SEE SBC 1021.1 |
|