| Plan Review Notes For Permit 01091291 |
| Permit Number |
01091291 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-22 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | GARAGE #1 ON SHEET AS-1 IS FED FROM | | | BLDG#1.ON SHEET ES-2,THEY ARE LISTED AS | | | GARAGE #2 FED FROM BLDG.#6.THE LOAD | | | CALCULATION MATCHES FROM PANEL "H" | | | SCHEDULE ON E-T3.3. | | | | | | THIS PLAN IS PASSED WITH THE PROVISO | | | THAT THE PLAN BUILDING AND GARAGE | | | NUMBERS ARE CHANGED TO CORRELATE IN ALL | | | DRAWINGS AND THE PANEL SCHEDULES AND | | | THE PANELS THEY FEED ARE CORRECTLY | | | MARKED. | | | | | | THESE CHANGES NEED ARE TO BE MADE | | | BEFORE ANY INSPECTIONS ARE CALLED AS TO | | | AVOID CONFUSION AND A LOSS OF TIME FOR | | | THE INSPECTOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|