| Plan Review Notes For Permit 01091289 |
| Permit Number |
01091289 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-07 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-1 ALL SIGNED AND SEALED PLANS | | | SHALL HAVE ALL SHEETS SIGNED AND SEALED | | | AND ARE REQUIRED TO HAVE A TITLE BLOCK | | | ON THEM. | | | | | | 2) SHT P-1 WATER RISER DIAGRAM AIR CHAM- | | | BERS SHALL BE ACCESSIBLE AND RECHARGEA- | | | BLE PER SPC SEC 607.8.3. SEE ATTACHED | | | SHEET FOR APPROVED AIR CHAMBERS. APPROV- | | | ED WATER HAMMER ARRESTORS DO NOT REQUIRE | | | ACCESS AND ARE RECOMMENDED. SIZE AND | | | LOCATION PER PDI-WH 201 IN AN EFFECTIVE | | | RANGE CLOSE TO LAST FIXTURE NOT AT TOP | | | OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|