| Plan Review Notes For Permit 01091289 |
| Permit Number |
01091289 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-19 00:00:00 | 1) PLANS DO NOT INDICATE EMERGENCY | | | LIGHTING OR ILLUMINATED EXIT SIGNS. | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | PROVIDED WITH PLANS. | | | 3) PLEASE PROVIDE MORE DETAILS ON | | | MOVABLE WIRE ENCLOSURE SHOWN ON | | | PAGE A-2. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER REMODEL. | | | 5) NO ELECTRICAL OR HVAC DRAWINGS | | | SUBMITTED WITH PLANS. | | | 6) PLEASE PROVIDE A PROPOSED | | | FITNESS EQUIPMENT PLANNED FOR THE ROOM. | | | 7) PLEASE INDICATE OCCUPANT LOAD,AND | | | TRAVEL DISTANCES TO EXIT ON THE PLANS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|