Plan Review Notes
Plan Review Notes For Permit 01091289
Permit Number 01091289
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-29 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FIXTURES PER SPC-94 TABLE 407. SHOW
 ALL EXISTING TOILET ROOMS WITH ALL THE
 DEMENTIONS FOR ROOMS, STALLS, DOOR SIZE
 ECT. 1ST AND 2ND FLOORS
 2) SHOW NEW TOILET ROOMS WITH ALL DEMEN-
 TIONS, CLEAR FLOOR SPACES, GRAB BAR DE-
 TAILS ECT. SHOW COMPLIANCE WITH ALL SEC-
 TIONS OF FACBC-97 SECTIONS. SHOW DETAILS
 3) URNALS TO COMPLY WITH FACBC SEC 4.18
 PLEASE SHOW DETAILS.
 4) FLOOR DRAINS ARE REQUIRED PER SPC SEC
 409.4.1.1 AND SHALL HAVE TRAP PRIMERS.
 5) PLEASE SUPPLY A SANITARY AND WATER
 RISER DIAGRAM FOR DEMO AND NEW WORK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377