| Plan Review Notes For Permit 01091289 |
| Permit Number |
01091289 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-29 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLEASE SUBMIT CALCULATIONS FOR MINI- | | | MUM FIXTURES PER SPC-94 TABLE 407. SHOW | | | ALL EXISTING TOILET ROOMS WITH ALL THE | | | DEMENTIONS FOR ROOMS, STALLS, DOOR SIZE | | | ECT. 1ST AND 2ND FLOORS | | | 2) SHOW NEW TOILET ROOMS WITH ALL DEMEN- | | | TIONS, CLEAR FLOOR SPACES, GRAB BAR DE- | | | TAILS ECT. SHOW COMPLIANCE WITH ALL SEC- | | | TIONS OF FACBC-97 SECTIONS. SHOW DETAILS | | | 3) URNALS TO COMPLY WITH FACBC SEC 4.18 | | | PLEASE SHOW DETAILS. | | | 4) FLOOR DRAINS ARE REQUIRED PER SPC SEC | | | 409.4.1.1 AND SHALL HAVE TRAP PRIMERS. | | | 5) PLEASE SUPPLY A SANITARY AND WATER | | | RISER DIAGRAM FOR DEMO AND NEW WORK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|