| Notes |
| Date |
Text |
| 2001-10-11 00:00:00 | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE PLANS AND THE FOLLOWING | | | INFORMATION WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | | | | 1.ENERGY CALCS WITH MANUAL J CALCS FOR | | | SIZING OF THE HVAC SYSTEM. | | | | | | 2.MODEL, BTUS, HEAT STRIP, AND SEER | | | OF THE AHU/C.U. | | | | | | 3.DUCTWORK, INDICATE SIZE, R-VALUE | | | CFM TO EACH ROOM AND SIZE OF GRIILS. | | | | | | 4.INDICATE HOW AHU IS SUPPPORTED IN | | | THE GARAGE. | | | | | | 5.INDICATE LINE SIZE, MATERIAL OF AND | | | PATH OF ALL PIPING. | | | | | | 6.TERMINATION OF CONDENSATE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|