| Plan Review Notes For Permit 01091267 |
| Permit Number |
01091267 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT 01091267 | | | 1414 8TH ST | | | O/B BRENDA WINN | | | | | | 1) SBC COMPONENTS & CLADDING,1606.2.6.2 | | | (2 COPIES) OF PRODUCT TESTING REPORTS | | | ARE REQUIRED FOR : | | | A) WINDOWS TESTED FOR WIND ONLY IF | | | SHUTTERED | | | B) STORM SHUTTERS | | | C) EXTERIOR DOORS, BOTH SLIDING & SWING | | | D) ROOFING, FIBERGLASS SHINGLES | | | | | | 2) BALCONY; | | | A- WHAT TYPE OF DECKING SHALL BE USED? | | | B- GUARDRAILS,1015.3. PICKETS THAT | | | WILL NOT ALLOW A 4" SPHERE TO PASS | | | THROUGH, ALSO DETAIL BOTTOM RAIL | | | THAT WILL NOT ALLOW A 2" SPHERE TO | | | PASS BETWEN THE DECK & BOTTOM RAIL. | | | | | | 3) SBC 2305.2.2 DRAFT STOPPING, | | | FLOOR/ CEILING ASSEMBLIES (500'). | | | | | | 4) SBC 2309.6 ACCESS TO ATTIC SPACE. | | | | | | 5) O/B TO SUBMIT PLANS TO COUNTY FOR | | | IMPACT FEE ASSESSMENT (COUNTY BUILDING | | | DEPARTMENT). | | | | | | 6) HAZARDOUS LOCATION MASTER BATH WINDOW | | | NEXT TO TUB. SBC 2405.2 REQUIURES | | | TEMPERED GLASS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|