| 2001-10-03 00:00:00 | ******** ****** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | AIC RATING IS HSOWN FOR PANEL BUT NOT |
| | MAIN DISCONNECT. |
| | |
| | 2)NOTE:PLEASE NOTE THAT PLANS DO NOT |
| | SHOW A MAIN DISC AND PANEL SCHEDULE |
| | SHOWS MCB PANEL?? PLEASE CLARIFY. |
| | |
| | 3)NOTE: PLEASE NOTE THAT SD OUTSIDE |
| | BATHS NEED TO BE A MIN OF 3'.NFPA-72, |
| | 2-5.2.1.6 |
| | |
| | 4) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 5)(PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF |
| | DISCONNECTAND PANEL(S). EQUIPMENT |
| | GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 6) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 7) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. |
| | |
| | 8)NOTE: PLEASE NOTE THAT NOT ON THE |
| | PLAN MENTIONS, "ALL BATH AND GARAGE |
| | OUTLETS |
| | ARE TO BE GFI PER 210-11-C-3" |
| | PLEASE NOTE THAT THIS ART;IS FOR |
| | OUTLETS IN BATHS TO BE 20A AND #12. |
| | THE ART FOR BATH AND GARAGE OUTLETS |
| | BEING GFI IS 210-8. PLEASE CORRECT. |
| | |
| | 9)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS PANEL AT 200AMPS? AND PANEL |
| | SCHEDULE IS SHOWN AT 150A, PLEASE |
| | CORRELATE. |
| | |
| | 10)NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS SHOWN ARE NOT DONE TO NEC |
| | ART;220 |
| | PLEASE CORRECT. |
| | |
| | 11)NOTE: PLEASE ALSO NOTE THAT TWO CODE |
| | ARTS ARE REFERENCED AT THE TOP OF THE |
| | PANEL SCHEDULES," 110-1 AND 215-C??? |
| | PLEASE CLARIFY WHERE OR WHAT THESE ARTS |
| | ARE?? NOT IN THE "99" NEC. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |