Plan Review Notes
Plan Review Notes For Permit 01091267
Permit Number 01091267
Review Stop B
Sequence Number 1
Notes
Date Text
2001-10-23 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01091267
 1414 8TH ST
 O/B BRENDA WINN
 TEL: 655-2672
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS /STANDARD BUILDING CODE
  
 1)- SBC 104.2.2* ADDITIONAL INFORMATION:
 THE DESIGNER'S NAME, SIGNATURE, TELE-
 PHONE NUMBER & ADDRESS ON PLAANS
  
 2)- THE PLANS ARE NOT DESIGNED BY AN
 ARCHITECT OR ENGINEER, THEREFORE THE
 PLAN REVIEW HAS TO BE COMPLETED UNDER
 THE SBCCI PRESCRIPTIVE CODE, STANDARD
 FOR HURRICANE RESISTANT RESIDENTIAL
 CONSTRUCTION SSTD 10-97.
  
 3)- SHEET A-3 WIND ENGINEERING IS CALCU-
 LATED USING THE ASCE 7-98 WHICH WILL NOT
 TAKE AFFECT UNTIL THE 2001 FLORIDA CODE
 IS ADOPTED, JAN.1,2002. WE ARE UNDER THE
 110HPH WIND ZONE. THIS BUILDING IA ALSO
 UNDER 60' TALL AND WOULD BE REVIEWED
 USING CHAPTER 16 OF SBCCI NOT ASCE 7-95.
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY REQUIRES (2 COPIES) OF PRODUCT
 TESTING REPORTSFOR THE FOLLOWING ITEMS:
 WINDOWS
 WINDOW MULLIONS (TO AJOIN 2 WINDOWS)
 DOORS EXTERIOR SWING
 DOORS SLIDERS
 DOORS OVERHEAD GARAGE
 ROOFING SHINGLES
 STORM SHUTTERS
 EITHER SBCCI REPORTS OR DADE COUNTY
 PRODUCT APPROVAL REPORTS ARE ACCEPTED.
  
 5)- SHEET 1 DETAIL "B" DEPICTS 2 TYPES
 OF CONSTRUCTIONA BEAM WHERE 4 BAR HOOPED
 COLUMNS ARE USED, 2ND WHERE THE VERTICAL
 STEEL IS PLACED AT 4'-0" O/C AND BEAM
 BLOCK ARE USED, FOR 2 STORY CONSTRUCTION
 A DOUBLE BEAM BLOCK IS USED WITH THE
 APPROPRIATE STEEL AND GROUT IS USED TO
 FILL THE BOND BEAM & FILLED CELLS.
  
 6)- ALSO MISSING IS THE CONTINUOUS
 ANCHORING FROM THE BOND BEAM, RIM JOIST,
 OR END TRUSS THAT THE FLOOR SYSTEM TIES
 INTO,THE CONTINUOUS STRAPPING THROUGH
 INTO THE TTRUSSES.
  
 7)- SBC 1606.1 DESIGN INFORMATION FOR
 THE TRUSSESIS IN COMPLETE, MISSING INFO:
 MEAN ROOF HEIGTH, TRUSS PLAN LAYOUT WITH
 THE WIND LOAD ASSUMPTION OF THE
 DESIGNER OF RECORD. THE HURRICANE ANCHOR
 SCHEDULE, GIVING THE LOADS, DIRECTION,
 MAGNITUDE OF LOADSTO BE RESISTED. MANU-
 FACTURE OF THE HURRICANE ANCHOR,MODEL NO
 THE GAUGE, AVERAGE UPLIFT ETC
  
 8)- PROVIDED IS A COPY OF THE SBCCI
 SSTD10-93/ 97 FORM USED TO DO A COMPLETE
 REVIEW.YOUR PLANS ARE NOT COMPLETE
 ENOUGH TO DO A REVIEW.
 A COPY OF THE CITIES INTERPRETATION
 FOR THE IMPLEMENTATION OF HURRICANE MISS
 LE IMPACT PROTECTION STANDARDS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412