| Plan Review Notes For Permit 01091257 |
| Permit Number |
01091257 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-10 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED | | | CLARIFICATION. PLANS ARE BEING SUBMITTED | | | FOR COMMERCIAL OFFICES/SPACE AND PLANS | | | LOAD CALCULATIONS ARE SHOWN FOR RESIDENT | | | -IAL??? PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S NEED TO BE SHOWN ON PLANS | | | FOR COMM SPACE. NEED TO CORRELATE WITH | | | PANEL SCHEDULE. 215-5 | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | A/C CU. 309.1 AND 210-63 | | | | | | 4)NOTE: PLEASE NOTE NO LIGHTING SHOWN? | | | EGRESS? EMERGENCY? EXIT? | | | | | | PLEASE CALRIFY AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW.IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | NOTE: CHANGE OF USE TO OFFICE, ALL | | | WIRING METHODS EXISTING AND NEW WILL BE | | | REQ`D TO MEET COMM WIRING METHODS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|