Plan Review Notes
Plan Review Notes For Permit 01091257
Permit Number 01091257
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-10 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED
 CLARIFICATION. PLANS ARE BEING SUBMITTED
 FOR COMMERCIAL OFFICES/SPACE AND PLANS
 LOAD CALCULATIONS ARE SHOWN FOR RESIDENT
 -IAL??? PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S NEED TO BE SHOWN ON PLANS
 FOR COMM SPACE. NEED TO CORRELATE WITH
 PANEL SCHEDULE. 215-5
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C CU. 309.1 AND 210-63
  
 4)NOTE: PLEASE NOTE NO LIGHTING SHOWN?
 EGRESS? EMERGENCY? EXIT?
  
 PLEASE CALRIFY AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW.IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
 NOTE: CHANGE OF USE TO OFFICE, ALL
 WIRING METHODS EXISTING AND NEW WILL BE
 REQ`D TO MEET COMM WIRING METHODS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372