| Plan Review Notes For Permit 01091228 |
| Permit Number |
01091228 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | *************BUILDING UNSAT************* | | | | | | SBC 104.2.2 | | | | | | 1. NEED SITE SPECIFIC ENGINEERING SIGNED | | | AND SEALED FOR GARAGE DOOR & "PEDESTRIAN | | | DOOR" & WINDOW TO SHOW COMPLIANCE WITH | | | WIND LOAD PER SBC 1997 | | | | | | 2. NEED PRODUCT APPROVALS FOR ROOFING. | | | | | | 3. PLANS ARE NOT CLEAR ON ATTACHMENT | | | OF NEW WALLS TO EXISTING GARAGE. | | | | | | 4. SHOW TYPE OF STRAPS IN TYPICAL WALL | | | SECTION TOP & BOTTOM. | | | | | | 5. NO ELECTRIC SHOWN.ELECTRIC TO BE | | | APPLIED FOR SEPARATELY WITH PLANS. | | | | | | 6.IS WALL THAT IS BEING REMOVED BEARING? | | | NEED RAFTER LAYOUT WITH ATTACHMENTS | | | SHOWN. | | | | | | 7. NEED DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 659-8096 EXT. 8394 |
|