Plan Review Notes
Plan Review Notes For Permit 01091228
Permit Number 01091228
Review Stop B
Sequence Number 1
Notes
Date Text
2001-10-22 00:00:00*************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1. NEED SITE SPECIFIC ENGINEERING SIGNED
 AND SEALED FOR GARAGE DOOR & "PEDESTRIAN
 DOOR" & WINDOW TO SHOW COMPLIANCE WITH
 WIND LOAD PER SBC 1997
  
 2. NEED PRODUCT APPROVALS FOR ROOFING.
  
 3. PLANS ARE NOT CLEAR ON ATTACHMENT
 OF NEW WALLS TO EXISTING GARAGE.
  
 4. SHOW TYPE OF STRAPS IN TYPICAL WALL
 SECTION TOP & BOTTOM.
  
 5. NO ELECTRIC SHOWN.ELECTRIC TO BE
 APPLIED FOR SEPARATELY WITH PLANS.
  
 6.IS WALL THAT IS BEING REMOVED BEARING?
 NEED RAFTER LAYOUT WITH ATTACHMENTS
 SHOWN.
  
 7. NEED DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394