Plan Review Notes
Plan Review Notes For Permit 01091150
Permit Number 01091150
Review Stop B
Sequence Number 4
Notes
Date Text
2002-03-27 00:00:00THE PLANS SUBMITTED 3/22/02 DO NOT
 COMPLY WITH THE CODE.THE PLANS
 IDENTIFIED AS 07286970 ON THE LISTING
 AGENCY STAMP INDICATE THE FOLLOWING:
  
 SHEET 1 OF 4 WIND VELOCITY 130 MPH ASCE
 7-98.(AS NOTED PREVIOUSLY WPB IS IN
 AN140 MPH ZONE)
  
 SHEET 2 OF 4 WIND VELOCITY 110 MPH
  
 SHEET 3 OF 4 WIND VELOCITY 130 MPH ASCE
 7-98
  
 ALL OF THESE SHEETS ARE SIGNED AND
 SEALED BY JOHN BODZIAK, ARCH.
  
 THERE IS NO SHEET NUMBERED 4 OF 4.
  
 ANOTHER SHEET SIGNED AND SEALED BY
 BODZIAK DATED 3/19/02, PAGE 1 OF 1,
 BEARING "APPROVAL NUMBER 001092"
 CONTAINS SOME FOUNDATION INFORMATION.
  
 THIS SHEET DECLARES 140 MPH ASCE 7-98
 AND 2001 FBC.
  
 FOR THE CITY TO ACCEPT THIS STRUCTURE
 IN ACCORDANCE WITH THE MANUFACTURED
 BUILDING ACT OF 1979, THE PLANS MUST
 MEET THE CRITERIA CONTAINED IN THAT
 LEGISLATION AND THE FLORIDA
 ADMINISTRATIVE CODE.TO DATE THE PLANS
 SUBMITTED HAVE NOT.PLEASE PROVIDE
 PLANS LISTED FOR USE IN THIS AREA.
 INCLUDE A COPY OF THE DCA LISTING
 RECOGNITION LETTER.
  
 COMPLETE CALCULATIONS FOR THE
 FOUNDATION WERE REQUESTEED PREVIOUSLY
 AND TO DATE THIS HAS NOT BEEN DONE.
 I HAVE REVIEWED THE SLIDING AND
 OVERTURNING ANALYSIS PREPARED BY
 KENNETH GODFREY, PE.IN A PHONE
 COVERSTION TODAY HE TOLD ME HE IS NOT
 RESPONSIBLE FOR THE FOUNDATION DESIGN.
  
 PROVIDE A DCA APPROVAL LETTER PERTINENT
 TO THESE PLANS.