Plan Review Notes
Plan Review Notes For Permit 01091150
Permit Number 01091150
Review Stop B
Sequence Number 3
Notes
Date Text
2002-03-11 00:00:00THE CITY OF WEST PALM BEACH IS LOCATED
 IN THE 140 MPH WIND CONTOUR.SEE FIG.
 6-1B OF ASCE 7-98.
  
 STATE CLEARLY WHICH CODE THIS STRUCTURE
 HAS BEEN DESIGNED TO.SBC 1997 SECTION
 1606 HAS DIFFERENT WIND DESIGN
 REQUIREMENTS THAN ASCE7-98 AND CLEARLY
 PROHIBITS THE MIXING OF WIND LOADS FROM
 DIFFERENT SOURCES.SEE SBC 1606.1.2.1
 (1997)
  
 THE K.A. GODFREY, PE CALCULATIONS ARE
 130 MPH AND DECLARE EXPOSURES C AND D.
 GIVENTHE PROPOSED SITING, PLEASE
 CLARIFY THESE CHOICES AND THE
 DIRECTIONS FROM WHICH THEY WILL BE
 APPLIED.
  
 THE JA BODZIAK, ARCH FOUNDATION PLAN
 DATED 2/4/02 MIXES WIND LOAD SOURCES
 AND CODES.THE PIER CALCUALTION HAS
 ONLY GRAVITY LOADS.SEE SBC 1609.1
 AND/OR ASCE 7-98 2.0 COMBINATION OF
 LOADS.
  
 SHEET 4.3 OF THE GODFREY CALCULATIONS
 HAS THE TIE DOWNS SPACED AT 6.19' MAX.
 THE BODZIAK AT 7.5'
  
 THE BODZIAK FOUNDATION PLAN CALLS OUT
 2000 PSF SOIL BEARING CAPACITY.
  
 PLEASE REVIEW CHAPTER 61G15-30
 OF THE FLORIDA ADMINISTRATIVE CODE,
 "RESPONSIBILITY RULES COMMON TO ALL
 ENGINEERS"
  
 PROVIDE A BUILDING LISTED FOR USE IN
 THIS AREA.1997 SBC 110 MPH (1606) OR
 ASCE 7-95 (INVOKED BY THE 97 SBC) 140
 MPH.
  
 OR THE 2001 FBC 140 MPH WIND ZONE.
  
 PROVIDE A FOUNDATION DESIGN, WITH
 COMPLETE CALCUALTIONS IN ACCORDANCE
 WITH GOOD ENGINEERING PRACTICE.
  
 IF THIS BUILDING IS TO HAVE THE FLOOR
 LEVEL SET AT THE SAME HEIGHT AS THE
 SURROUNDING GRADE, HOW WILL THE 18"
 CLEARANCE TO GRADE CALLED OUT ON THE
 FOUNDATION SHEET BE ACCOMPLISHED?SEE
 ALSO, SBC 2303.3 AND 2304.2.5.