| Plan Review Notes For Permit 01091140 |
| Permit Number |
01091140 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-17 00:00:00 | CHECKLIST: | | | 1-SEE COMMENTS BY PLUMBING. SAME COMMENT | | | WAS ADDRESSED SEVERAL TIMES BEFORE. | | | 2-NEED NOTICE OF COMMENCEMENT. | | | 3-WILL NEED ADDITIONAL SOIL BORINGS FOR | | | EACH STRUCTURE AS RECOMMENDED ON THE | | | PRELIMINARY SOIL TEST REPORT. | | | 4-PROVIDE PRODUCT APPROVAL FOR: | | | A)GARAGE DOORS PRODUCT APPROVAL WAS | | | DELETED FROM SBCCI. | | | B)WINDOW MULLIONS. | | | | | | 5-CLEARLY INDICATE OPTIONS TO BE BUILT | | | AND PROVIDE CORRESPONDING PRODUCT | | | APPROVAL OR CROSS OUT SHEET. | | | 6-OWES ADDITIONAL FEES FOR UPDATED | | | VALUATION AND RADON FEES. PLEASE, PAY | | | ATTACHED RECEIPTS. | | | 7-PROVIDE CERTIFICATION FOR 2 HR FIRE | | | RATED CONCRETE BLOCK USED TO SEPARATE | | | TOWNHOUSES. SEE SEC. 709.3 SBC 1997. | | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS OR APPLY FOR SEPARATE PERMIT. | | | | | | NOTES: | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091140, 01091144, 01091147, 01091148, | | | 01091146 AND 01091143. | | | -DRAWINGS TO BE FILED UNDER PERMIT # | | | 01091140. |
|