Plan Review Notes
Plan Review Notes For Permit 01091019
Permit Number 01091019
Review Stop B
Sequence Number 3
Notes
Date Text
2001-11-14 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEERED TRUSSES ARE DESIGNED USING
 DIFFERENT MEAN ROOF HEIGHTS. THERE IS
 ONLY ONE MEAN ROOF HEIGHT FOR ENTIRE
 BUILDING. REVIEW ALL ENGINEERED
 TRUSSES AND REVISE AS REQUIRED.
 TABLE 1606.2A SBC 1997.
 2-SOME TRUSSES ARE DESIGNED USING WALL
 HEIGHT. THIS APPLIES TO FLAT ROOF.
 USE MEAN ROOF HEIGHT FOR SLOPED ROOF.
 REVISE AS REQUIRED.
 3-GENERAL DETAILS:
 A)THERE ARE TWO DIFFERENT ENGINEERS.
 COMPLY WITH REQUIREMENTS OF CHAPTER
 471 FL. STATUTES WHEN CHANGING ENG'R.
 B)UPDATE GENERAL DETAILS AS REQUIRED.
 C)DETAILS & SPECS ARE NOT LEGIBLE.
  
  
 NOTES:
 -THESE COMMENTS HAVE BEING ADDRESSED ON
 PREVIOUS REVIEWS.
 -DRAWINGS TO BE FILED UNDER PERMIT #
 01091019.
 -COMMENTS APPLY TO PERMIT #S:
 01091019, 01091025, 01091042, 01091054
 AND 01091060.