| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-REVISE ENERGY CALCULATIONS: | | | A)THIS IS A COMPUTER PROGRAM. CHANGES BY | | | HAND ARE NOT ALLOWED BECAUSE THEY WILL | | | ALTER THE ACTUAL CALCULATIONS. | | | SEE NUMBER OF UNITS AND NUMBER OF | | | BEDROOMS AND REVISE ORIGINAL FORM | | | AS REQUIRED. | | | | | | | | | 2-REVISE THE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE FORM. THE | | | MEAN ROOF HEIGHT AND THE DESIGN | | | PRESSURES DON'T MATCH. SEE TABLE | | | 1606.2A SBC 1997. | | | | | | 3-PROVIDE CERTIFICATION FOR TWO HOUR | | | FIRE RATED CONCRETE BLOCK BETWEEN | | | TOWNHOUSES IN ACCORDANCE WITH SECTION | | | 709.3 SBC 1997. | | | | | | | | | | | | | | | | | | | | | NOTES: | | | -DRAWINGS TO BE FILED UNDER PERMIT # | | | 01091019. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091019, 01091025, 01091042, 01091054 | | | AND 01091060. |
|