Plan Review Notes
Plan Review Notes For Permit 01091004
Permit Number 01091004
Review Stop P
Sequence Number 1
Notes
Date Text
2001-09-26 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
  
 1) PLEASE NOTE THAT PLANS NEED TO BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD PER FS/FAC 471.025
 2) PAGE A-1, PLEASE PROVIDE CALCULATIONS
 FOR MINIMUM FACILITIES PER SPC-94 TABLE
 407.
 3) PAGE A-1, EXISTING BATHROOM SHOWER
 DOES NOT MEET FACBC-97 SECTION 4.21 REQ-
 UIREMENTS.
 4) PAGE A-1, COMMONS AREA, SINK TO COM-
 PLY WITH FACBC-97 SECTION 4.24.
 5) PAGE A-1, WATER HEATER TO BE READILY
 ACCESSIBLE. PROVIDE DETAILS.
 6) PAGE A-1, PLEASE PROVIDE SANITARY
 RISER DIAGRAM FOR NEW HDCP BATHROOMS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377